4.1.4.5
Connecting the cable shields (FSA ... FSG only)
For EMC-compliant wiring, you must connect the cable shields to the shield plate of the
converter.
Use shielded cables for the following connection:
● Communication cable
● Control cable
● Motor cable
Before connecting the cable shields, you need to strip the cable insulation.
The following illustrations take converters with PROFINET interfaces as examples.
Connecting the cable shields, FSA ... FSC converters
The shield support for converter FSB is displayed as
an example.
①
Unshielded line cable
②
Cable tie
③
Unshielded communication cable
④
Unlacquered, good electrically conducting
mounting plate
⑤
Shielded control cable
⑥
Toothed tape
⑦
Shielded motor cable
Wiring
4.1 Line supply and motor
SINAMICS G120X converter
96
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC