p2170[0...n]
Current threshold value / I_thres
Access level: 3
Calculated:
CALC_MOD_LIM_REF
Data type: FloatingPoint32
Can be changed: T, U
Scaling: p2002
Dynamic index: DDS, p0180
Unit group: 6_2
Unit selection: p0505
Function diagram: 8022
Min:
0.00 [Arms]
Max:
10000.00 [Arms]
Factory setting:
0.00 [Arms]
Description:
Sets the absolute current threshold for the messages.
"I_act >= I_threshold p2170" (BO: r2197.8)
"I_act < I_threshold p2170" (BO: r2198.8)
Dependency:
See also: p2171
p2171[0...n]
Current threshold value reached delay time / I_thresh rch t_del
Access level: 3
Calculated: -
Data type: Unsigned16
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: 8022
Min:
0 [ms]
Max:
10000 [ms]
Factory setting:
10 [ms]
Description:
Sets the delay time for the comparison of the current actual value (r0068) with the current threshold value (p2170).
Dependency:
See also: p2170
p2172[0...n]
DC link voltage threshold value / Vdc thresh val
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: p2001
Dynamic index: DDS, p0180
Unit group: 5_2
Unit selection: p0505
Function diagram: -
Min:
0 [V]
Max:
2000 [V]
Factory setting:
800 [V]
Description:
Sets the DC link voltage threshold value for the following messages:
"Vdc_act <= Vdc_threshold p2172" (BO: r2197.9)
"Vdc_act > Vdc_threshold p2172" (BO: r2197.10)
Dependency:
See also: p2173
p2173[0...n]
DC link voltage comparison delay time / t_del Vdc
Access level: 3
Calculated: -
Data type: Unsigned16
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: -
Min:
0 [ms]
Max:
10000 [ms]
Factory setting:
10 [ms]
Description:
Sets the delay time for the comparison of the DC link voltage r0070 with the threshold value p2172.
Dependency:
See also: p2172
p2175[0...n]
Motor blocked speed threshold / Mot lock n_thresh
Access level: 3
Calculated:
CALC_MOD_LIM_REF
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: 3_1
Unit selection: p0505
Function diagram: 8012
Min:
0.00 [rpm]
Max:
210000.00 [rpm]
Factory setting:
120.00 [rpm]
Description:
Sets the speed threshold for the message "Motor blocked" (BO: r2198.6).
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
783