In‐
stance
ID
Object name
Description
Unit
Range
Access
type
1)
Parameter
AV21
PREV FAULT 3
Number of the fault third from last ---
converter-depend‐
ent
R
r0947[3]
AV22
PREV FAULT 4
Number of the fault fourth from
last
---
converter-depend‐
ent
R
r0947[4]
AV25
SEL STPT
Command to select the setpoint
source
---
0 … 32767
W
p1000
AV28
AO1 ACT
Signal from AO 1
mA
converter-depend‐
ent
R
r0774.0
AV29
AO2 ACT
Signal from AO 1
mA
converter-depend‐
ent
R
r0774.1
AV30
MIN Speed
Minimum speed
RPM
0.000 – 19500.000 W
p1080
AV31
MAX Speed
Maximum speed
RPM
0.000 … 210000.00
0
W
p1082
AV32
ACCEL TIME
Ramp-up time
s
0.00 … 999999.0
W
p1120
AV33
DECEL TIME
Ramp-down time
s
0.00 … 999999.0
W
p1121
AV34
CUR LIM
Current limit
A
converter-depend‐
ent
R
p0640
AV39
ACT WARN
Indication of a pending alarm
---
converter-depend‐
ent
R
r2110[0]
AV40
PREV WARN 1
Indication of the last alarm
---
converter-depend‐
ent
R
r2110[1]
AV41
PREV WARN 2
Indication of the last but one
alarm
---
converter-depend‐
ent
R
r2110[2]
AV5000 RAMP UP TIME
Technology controller ramp-up
time
s
0 … 650
W
p2257
AV5001 RAMP DOWN TIME
Technology controller ramp-
down time
s
0 … 650
W
p2258
AV5002
FILTER TIME
Technology controller actual val‐
ue filter time constant
s
0 … 60
W
p2265
AV5003 DIFF TIME
Technology controller differentia‐
tion time constant
s
0 … 60
W
p2274
AV5004 PROP GAIN
Technology controller propor‐
tional gain
s
0 … 1000
W
p2280
AV5005 INTEG TIME
Technology controller integral
time
s
0 … 1000
W
p2285
AV5006 OUTPUT MAX
Technology controller maximum
limiting
%
- 200 … 200
W
p2291
AV5007 OUTPUT MIN
Technology controller minimum
limiting
%
- 200 … 200
W
p2292
AV5100 RAMP UP TIME 0
Technology controller 0 ramp-up
time
s
0 … 650
W
p11057
AV5101 RAMP DOWN TIME 0 Technology controller 0 ramp-
down time
s
0 … 650
W
p11058
AV5102 FILTER TIME 0
Technology controller 0 actual
value filter time constant
s
0 … 60
W
p11065
Advanced commissioning
6.3 Drive control
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
285