Description:
For the energy-saving display of a fluid-flow machine, a typical flow characteristic P = f(n) with 5 points along the
characteristic is required.
This parameter specifies the speed (n) of point 5 as a [%].
Dependency:
See also: r0041, p3320, p3321, p3322, p3323, p3324, p3325, p3326, p3327, p3328
Note
The reference value for power and speed is the rated power/rated speed.
The energy saved is displayed in r0041.
p3330[0...n]
BI: 2/3 wire control command 1 / 2/3 wire cmd 1
Access level: 3
Calculated: -
Data type: Unsigned32 / Binary
Can be changed: T, U
Scaling: -
Dynamic index: CDS, p0170
Unit group: -
Unit selection: -
Function diagram: 2272, 2273
Min:
-
Max:
-
Factory setting:
0
Description:
Sets the signal source for command 1 for the two-wire control/three-wire control.
Dependency:
See also: p0015, p3331, p3332, r3333, p3334
Note
The mode of operation of this binector input is dependent on the wire control set in p0015.
p3331[0...n]
BI: 2/3 wire control command 2 / 2/3 wire cmd 2
Access level: 3
Calculated: -
Data type: Unsigned32 / Binary
Can be changed: T, U
Scaling: -
Dynamic index: CDS, p0170
Unit group: -
Unit selection: -
Function diagram: 2272, 2273
Min:
-
Max:
-
Factory setting:
0
Description:
Sets the signal source for command 2 for the two-wire control/three-wire control.
Dependency:
See also: p0015, p3330, p3332, r3333, p3334
Note
The mode of operation of this binector input is dependent on the wire control set in p0015.
p3332[0...n]
BI: 2/3 wire control command 3 / 2/3 wire cmd 3
Access level: 3
Calculated: -
Data type: Unsigned32 / Binary
Can be changed: T, U
Scaling: -
Dynamic index: CDS, p0170
Unit group: -
Unit selection: -
Function diagram: 2273
Min:
-
Max:
-
Factory setting:
0
Description:
Sets the signal source for command 3 for the two-wire control/three-wire control.
Dependency:
See also: p0015, p3330, p3331, r3333, p3334
Note
The mode of operation of this binector input is dependent on the wire control set in p0015.
r3333.0...3
CO/BO: 2/3 wire control control word / 2/3 wire STW
Access level: 3
Calculated: -
Data type: Unsigned32
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 2272, 2273
Min:
-
Max:
-
Factory setting:
-
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
837