p0809[0...2]
Copy Command Data Set CDS / Copy CDS
Access level: 2
Calculated: -
Data type: Unsigned8
Can be changed: T
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 8560
Min:
0
Max:
3
Factory setting:
0
Description:
Copies one Command Data Set (CDS) into another.
Index:
[0] = Source Command Data Set
[1] = Target Command Data Set
[2] = Start copying procedure
Dependency:
See also: r3996
NOTICE
When the command data sets are copied, short-term communication interruptions may occur.
Note
When copying a command data set (CDS), the values in p0700, p1000 and p1500 are not accepted. As a consequence,
the associated macros are not executed and inconsistencies are avoided.
Procedure:
1. In Index 0, enter which command data set should be copied.
2. In index 1, enter the command data set that is to be copied into.
3. Start copying: set index 2 from 0 to 1.
p0809[2] is automatically set to 0 when copying is completed.
p0810
BI: Command data set selection CDS bit 0 / CDS select., bit 0
G120X_DP,
G120X_PN
Access level: 2
Calculated: -
Data type: Unsigned32 / Binary
Can be changed: T
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 8560
Min:
-
Max:
-
Factory setting:
722.4
Description:
Sets the signal source to select the Command Data Set bit 0 (CDS bit 0).
Dependency:
See also: r0050, p0811, r0836
NOTICE
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note
The Command Data Set selected using the binector inputs is displayed in r0836.
The currently effective command data set is displayed in r0050.
A Command Data Set can be copied using p0809.
p0810
BI: Command data set selection CDS bit 0 / CDS select., bit 0
G120X_USS
Access level: 2
Calculated: -
Data type: Unsigned32 / Binary
Can be changed: T
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 8560
Min:
-
Max:
-
Factory setting:
0
Description:
Sets the signal source to select the Command Data Set bit 0 (CDS bit 0).
Dependency:
See also: r0050, p0811, r0836
NOTICE
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
583