p1909[0...n]
Motor data identification control word / MotID STW
Access level: 3
Calculated: CALC_MOD_ALL Data type: Unsigned32
Can be changed: T
Scaling: -
Dynamic index: MDS, p0130
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
0000 0000 0000 0000 0000
0000 0000 0000 bin
Description:
Sets the configuration for the motor data identification.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Stator inductance estimate no measurement
Yes
No
-
02
Rotor time constant estimate no measurement
Yes
No
-
03
Leakage inductance estimate no measurement
Yes
No
-
05
Determine Tr and Lsig evaluation in the time range
Yes
No
-
06
Activate vibration damping
Yes
No
-
07
Deactivate vibration detection
Yes
No
-
11
Deactivate pulse measurement Lq Ld
Yes
No
-
12
Deactivate rotor resistance Rr measurement
Yes
No
-
14
Deactivate valve interlocking time measurement
Yes
No
-
15
Determine only stator resistance, valve voltage fault, dead
time
Yes
No
-
16
Short motor identification (lower quality)
Yes
No
-
17
Measurement without control parameter calculation
Yes
No
-
18
After motID direct transition into operation
Yes
No
-
19
After MotID automatically save results
Yes
No
-
20
Estimate cable resistance
Yes
No
-
21
Calibrating the output voltage measurement
Yes
No
-
22
Only identify circle
Yes
No
-
23
Deactivate circle identification
Yes
No
-
24
Circle identification with 0 and 90 degrees
Yes
No
-
26
Measure with long cable
Yes
No
-
Note
The following applies to permanent-magnet synchronous motors:
Without de-selection in bit 11, in the closed-loop control mode, the direct inductance LD and the quadrature inductance
Lq are measured at a low current.
When de-selecting with bit 11 or in the U/f mode, the stator inductance is measured at half the rated motor current.
If the stator is inductance is not measured but is to be estimated, then bit 0 should be set and bit 11 should be de-
selected.
Bit 19 = 1:
All parameters are automatically saved after a successful motor data identification.
If a speed controller optimization run is then selected, the parameters are only saved after this measurement has been
completed.
Bit 22 ... 24: only for reluctance motors
Bit 22 = 1:
Only that measurement is carried out that is required for the flying restart of a reluctance motor. The bit is reset after
a successful measurement
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
721