p1037[0...n]
Motorized potentiometer maximum speed / MotP n_max
Access level: 3
Calculated:
CALC_MOD_LIM_REF
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: 3_1
Unit selection: p0505
Function diagram: 3020
Min:
-210000.000 [rpm]
Max:
210000.000 [rpm]
Factory setting:
0.000 [rpm]
Description:
Sets the maximum speed/velocity for the motorized potentiometer.
Note
This parameter is automatically pre-assigned in the commissioning phase.
The setpoint output from the motorized potentiometer is limited to this value (see function diagram 3020).
p1038[0...n]
Motorized potentiometer minimum speed / MotP n_min
Access level: 3
Calculated:
CALC_MOD_LIM_REF
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: 3_1
Unit selection: p0505
Function diagram: 3020
Min:
-210000.000 [rpm]
Max:
210000.000 [rpm]
Factory setting:
0.000 [rpm]
Description:
Sets the minimum speed/velocity for the motorized potentiometer.
Note
This parameter is automatically pre-assigned in the commissioning phase.
The setpoint output from the motorized potentiometer is limited to this value (see function diagram 3020).
p1039[0...n]
BI: Motorized potentiometer inversion / MotP inv
Access level: 3
Calculated: -
Data type: Unsigned32 / Binary
Can be changed: T
Scaling: -
Dynamic index: CDS, p0170
Unit group: -
Unit selection: -
Function diagram: 3020
Min:
-
Max:
-
Factory setting:
0
Description:
Sets the signal source to invert the minimum speed/velocity or the maximum speed/velocity for the motorized
potentiometer.
Dependency:
See also: p1037, p1038
Note
The inversion is only active during "motorized potentiometer raise" or "motorized potentiometer lower".
p1040[0...n]
Motorized potentiometer starting value / Mop start value
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: 3_1
Unit selection: p0505
Function diagram: 3020
Min:
-210000.000 [rpm]
Max:
210000.000 [rpm]
Factory setting:
0.000 [rpm]
Description:
Sets the starting value for the motorized potentiometer. This starting value becomes effective after the drive has been
switched on.
Dependency:
Only effective if p1030.0 = 0.
See also: p1030
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
617