9.3
Identification & maintenance data (I&M)
I&M data
The converter supports the following identification and maintenance (I&M) data.
I&M
data
Format
Explanation
Associated pa‐
rameters
Example for the
content
I&M0
u8[64] PROFIBUS
u8[54] PROFINET
Converter-specific data, read only -
See below
I&M1
Visible String [32]
Plant/system identifier
p8806[0 … 31] "ak12-
ne.bo2=fu1"
Visible String [22]
Location code
p8806[32 … 53] "sc2+or45"
I&M2
Visible String [16]
Date
p8807[0 … 15]
"2013-01-21
16:15"
I&M3
Visible String [54]
Any comment
p8808[0 … 53]
-
I&M4
Octet String[54]
Check signature to track changes
for Safety Integrated.
This value can be changed by the
user.
The test signature is reset to the
value generated by the machine if
p8805 = 0 is used.
p8809[0 … 53]
Values of
r9781[0] and
r9782[0]
When requested, the converter transfers its I&M data to a higher-level control or to a PC/PG
with installed STEP 7 or TIA Portal.
I&M0
Designation
Format
Example for the
content
Valid for PRO‐
FINET
Valid for PRO‐
FIBUS
Manufacturer-specific
u8[10]
00 … 00 hex
---
✓
MANUFACTURER_ID u16
42d hex (=Sie‐
mens)
✓
✓
ORDER_ID
Visible String
[20]
"6SL3246-0BA22-
1FA0"
✓
✓
SERIAL_NUMBER
Visible String
[16]
"T-R32015957"
✓
✓
HARDWARE_REVISION
u16
0001 hex
✓
✓
SOFTWARE_REVISION
char, u8[3]
"V" 04.70.19
✓
✓
REVISION_COUNTER
u16
0000 hex
✓
✓
PROFILE_ID
u16
3A00 hex
✓
✓
PROFILE_SPECIFIC_TYPE u16
0000 hex
✓
✓
IM_VERSION
u8[2]
01.02
✓
✓
IM_SUPPORTED
bit[16]
001E hex
✓
✓
Warnings, faults and system messages
9.3 Identification & maintenance data (I&M)
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC