2 Parameters
2.2 List of parameters
Dependency:
The number of statistic entries is displayed in p9220.
In p9221, the component Id can be set whose statistic is to be displayed.
Refer to: r9220, p9221
Note:
As a statistic entry comprises 5 data, when calling the entries via the terminal, a size that represents a multiple of 5
must be specified.
Example: the 2nd entry must be called:
rdp 1 9222 5 5
or
rdpa 1 9222 5 5.
Description:
Setting and display when memory card is "removed safely".
Procedure:
Setting p9400 = 2 results in a value of 3
--> The memory card can be removed safely. After removal the value sets itself to 0 automatically.
Setting p9400 = 2 results in a value of 100
--> The memory card cannot be removed safely. Removal may destroy the file system on the memory card. It may be
necessary to set p9400 = 2 again.
Value:
0:
No memory card inserted
1:
Memory card inserted
2:
Request "safe removal" of the memory card
3:
"Safe removal" possible
100:
"Safe removal" not possible due to access
Dependency:
Refer to: r9401
Notice:
Removing the memory card without a request (p9400 = 2) and confirmation (p9400 = 3) may destroy the file system
on the memory card. The memory card will then no longer work properly and must be replaced.
Note:
The status when the memory card is being "removed safely" is shown in r9401.
Re value = 0, 1, 3, 100:
These values can only be displayed, not set.
Description:
Displays the status of the memory card.
Dependency:
Refer to: p9400
Note:
Re bit 01, 00:
Bit 1/0 = 0/0: No memory card inserted (corresponds to p9400 = 0).
Bit 1/0 = 0/1: "Safe removal" possible (corresponds to p9400 = 3).
Bit 1/0 = 1/0: Status not possible.
Bit 1/0 = 1/1: Memory card inserted (corresponds to p9400 = 1, 2, 100).
p9400
Safely remove memory card / Mem_card rem
CU_DCP
Can be changed:
T
Access level:
2
Data type:
Integer16
Func. diagram:
-
Min Max
Factory
setting
0 100
0
r9401
Safely remove memory card status / Mem_card rem stat
CU_DCP
Can be changed:
-
Access level:
2
Data type:
Unsigned16
Func. diagram:
-
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Memory card inserted
Yes
No
-
01
Memory card activated
Yes
No
-
02
SIEMENS memory card
Yes
No
-
03
Memory card as USB data storage medium
from the PC used
Yes
No
-
Summary of Contents for sinamics dcp
Page 2: ......
Page 6: ...Preface SINAMICS DCP 6 List Manual LH21 05 2016 ...
Page 8: ...Table of contents SINAMICS DCP 8 List Manual LH21 05 2016 ...
Page 510: ...A Appendix A 2 List of abbreviations SINAMICS DCP 510 List Manual LH21 05 2016 ...
Page 516: ...Index SINAMICS DCP 516 List Manual LH21 05 2016 ...
Page 517: ...Siemens Parts ...