2 Parameters
2.2 List of parameters
SINAMICS DCP
224
List Manual (LH21), 05/2016
Re bit 02, 00:
Bit 2/0 = 0/0: No memory card inserted.
Bit 2/0 = 0/1: Memory card inserted, but not a SIEMENS memory card.
Bit 2/0 = 1/0: Status not possible.
Bit 2/0 = 1/1: SIEMENS memory card inserted.
Description:
Displays the parameters that were not able to be transferred when reading the parameter back-up files (PS files)
from the non-volatile memory (e.g. memory card).
r9406[0] = 0
--> All of the parameter values were able to be transferred error-free.
r9406[0...x] > 0
--> indicates the parameter number in the following cases:
- parameter, whose value was not able to be completely accepted.
- indexed parameter, where at least 1 index was not able to be accepted. The first index that is not transferred is
displayed in r9407.
Dependency:
Refer to: r9407, r9408
Note:
All indices from r9406 to r9408 designate the same parameter.
r9406[x] parameter number, parameter not accepted
r9407[x] parameter index, parameter not accepted
r9408[x] fault code, parameter not accepted
Description:
Displays the first index of the parameters that could not be transferred when the parameter backup files (PS files)
were read from the non-volatile memory (e.g. memory card).
If, from an indexed parameter, at least one index was not able to be transferred, then the parameter number is
displayed in r9406[n] and the first index that was not transferred is displayed in r9407[n].
r9406[0] = 0
--> All of the parameter values were able to be transferred error-free.
r9406[n] > 0
--> Displays r9407[n] the first index of the parameter number r9406[n] that was not transferred.
Dependency:
Refer to: r9406, r9408
Note:
All indices from r9406 to r9408 designate the same parameter.
r9406[x] parameter number, parameter not accepted
r9407[x] parameter index, parameter not accepted
r9408[x] fault code, parameter not accepted
Description:
Only for internal Siemens service purposes.
Dependency:
Refer to: r9406, r9407
r9406[0...19]
PS file parameter number parameter not transferred / PS par_no n transf
All objects
Can be changed:
-
Access level:
1
Data type:
Unsigned16
Func. diagram:
-
Min Max
Factory
setting
- -
-
r9407[0...19]
PS file parameter index parameter not transferred / PS parameter index
All objects
Can be changed:
-
Access level:
1
Data type:
Unsigned16
Func. diagram:
-
Min Max
Factory
setting
- -
-
r9408[0...19]
PS file fault code parameter not transferred / PS fault code
All objects
Can be changed:
-
Access level:
1
Data type:
Unsigned16
Func. diagram:
-
Min Max
Factory
setting
- -
-
Summary of Contents for sinamics dcp
Page 2: ......
Page 6: ...Preface SINAMICS DCP 6 List Manual LH21 05 2016 ...
Page 8: ...Table of contents SINAMICS DCP 8 List Manual LH21 05 2016 ...
Page 510: ...A Appendix A 2 List of abbreviations SINAMICS DCP 510 List Manual LH21 05 2016 ...
Page 516: ...Index SINAMICS DCP 516 List Manual LH21 05 2016 ...
Page 517: ...Siemens Parts ...