2 Parameters
2.2 List of parameters
SINAMICS DCP
246
List Manual (LH21), 05/2016
Description:
Sets the scaling for analog input 1 (AI 1, X177.27/28) on the CUD.
The value indicates the percentage value for mapping an input voltage of 10 V or an input current of 20 mA at the
analog input.
Example:
p50711 = 90%
--> 10 V or 20 mA is scaled to 90%
--> 5 V or 10 mA is equivalent to 45%
Note:
AI: Analog Input
Description:
Sets the offset for analog input 1 (AI 1, X177.27/28) on the CUD.
Note:
AI: Analog Input
Description:
Sets the signal processing mode for analog input 1 (AI 1, X177.27/28) on the CUD.
Value:
0:
Signal not influenced
1:
Signal absolute value generation
2:
Signal inverted
3:
Signal absolute value generation inverted
Note:
AI: Analog Input
Description:
Sets the signal source for inverting the signal from analog input 1 (AI 1, X177.27/28) on the CUD.
1 signal: inversion
0 signal: no inversion
Note:
AI: Analog Input
Description:
Sets the time constant for smoothing the signal from analog input 1 (AI 1, X177.27/28) on the CUD.
Note:
AI: Analog Input
p50711[0...n]
CUD analog input 1 scaling / CUD AI 1 scal
DCP_CTRL
Can be changed:
U, T
Access level:
3
Data type:
FloatingPoint32
Func. diagram:
2080
Min Max
Factory
setting
-1000.0 [%]
1000.0 [%]
100.0 [%]
p50712
CUD analog input 1 offset / CUD AI 1 offs
DCP_CTRL
Can be changed:
U, T
Access level:
3
Data type:
FloatingPoint32
Func. diagram:
2080
Min Max
Factory
setting
-200.00 [%]
200.00 [%]
0.00 [%]
p50713
CUD analog input 1 signal processing / CUD AI 1 sig proc
DCP_CTRL
Can be changed:
T
Access level:
3
Data type:
Integer16
Func. diagram:
2080
Min Max
Factory
setting
0 3
0
p50714
BI: CUD analog input 1 inversion / CUD AI 1 inv
DCP_CTRL
Can be changed:
T
Access level:
3
Data type:
Unsigned32 / Binary
Func. diagram:
2080
Min Max
Factory
setting
- -
0
p50715
CUD analog input 1 smoothing time constant / CUD AI 1 T
DCP_CTRL
Can be changed:
U, T
Access level:
3
Data type:
FloatingPoint32
Func. diagram:
2080
Min Max
Factory
setting
0 [ms]
10000 [ms]
0 [ms]
Summary of Contents for sinamics dcp
Page 2: ......
Page 6: ...Preface SINAMICS DCP 6 List Manual LH21 05 2016 ...
Page 8: ...Table of contents SINAMICS DCP 8 List Manual LH21 05 2016 ...
Page 510: ...A Appendix A 2 List of abbreviations SINAMICS DCP 510 List Manual LH21 05 2016 ...
Page 516: ...Index SINAMICS DCP 516 List Manual LH21 05 2016 ...
Page 517: ...Siemens Parts ...