2 Parameters
2.2 List of parameters
SINAMICS DCP
276
List Manual (LH21), 05/2016
Description:
Display and connector output for the voltage setpoint after the ramp-function generator.
Description:
Sets the signal source for activating the voltage controller.
Description:
Sets the rate time in the voltage actual value channel of the voltage controller.
Description:
Sets the smoothing time constant for the voltage actual value channel of the voltage controller.
Description:
Sets the width of the dead range in the setpoint-actual value difference channel for the "DC link buffering" function.
Dependency:
Refer to: p54146
Note:
The set value refers to the rated voltage of the SINAMICS DCP.
Description:
Sets the proportional gain Kp for the voltage controller.
Description:
Sets the integral time Tn for the voltage controller.
r54103
CO: Voltage controller setpoint after the ramp-function generator / U_ctr U_set af RFG
DCP_CTRL
Can be changed:
-
Access level:
2
Data type:
FloatingPoint32
Func. diagram:
6818
Min Max
Factory
setting
- [%]
- [%]
- [%]
p54105
BI: Voltage controller activation signal source / U_ctrl act s_src
DCP_CTRL
Can be changed:
T
Access level:
2
Data type:
Unsigned32 / Binary
Func. diagram:
6818
Min Max
Factory
setting
- -
0
p54121
Voltage controller actual value rate time / U_ctr act val Tv
DCP_CTRL
Can be changed:
U, T
Access level:
2
Data type:
FloatingPoint32
Func. diagram:
6818
Min Max
Factory
setting
0.00 [ms]
100.00 [ms]
10.00 [ms]
p54122
Voltage controller actual value smoothing time constant / U_ctrl act val T
DCP_CTRL
Can be changed:
U, T
Access level:
2
Data type:
FloatingPoint32
Func. diagram:
6818
Min Max
Factory
setting
0.00 [ms]
100.00 [ms]
2.00 [ms]
p54124
Voltage controller DC link buffering dead range / U_ctr VDC dead rng
DCP_CTRL
Can be changed:
U, T
Access level:
2
Data type:
FloatingPoint32
Func. diagram:
6818
Min Max
Factory
setting
0.00 [%]
100.00 [%]
0.00 [%]
p54125
Voltage controller proportional gain / U_ctrl Kp
DCP_CTRL
Can be changed:
U, T
Access level:
2
Data type:
FloatingPoint32
Func. diagram:
6818
Min Max
Factory
setting
0.001 30.000
2.000
p54126
Voltage controller integral time / U_ctrl Tn
DCP_CTRL
Can be changed:
U, T
Access level:
2
Data type:
FloatingPoint32
Func. diagram:
6818
Min Max
Factory
setting
0.01 [ms]
1000.00 [ms]
0.30 [ms]
Summary of Contents for sinamics dcp
Page 2: ......
Page 6: ...Preface SINAMICS DCP 6 List Manual LH21 05 2016 ...
Page 8: ...Table of contents SINAMICS DCP 8 List Manual LH21 05 2016 ...
Page 510: ...A Appendix A 2 List of abbreviations SINAMICS DCP 510 List Manual LH21 05 2016 ...
Page 516: ...Index SINAMICS DCP 516 List Manual LH21 05 2016 ...
Page 517: ...Siemens Parts ...