Description:
Sets the address for the commissioning interface (PPI).
Note:
Only odd-numbered addresses can be set.
Changes only become effective after POWER ON.
The parameter is not influenced by setting the factory setting.
Description:
Displays the receive errors at the commissioning interface (RS232).
Index:
[0] = Number of error-free telegrams
[1] = Number of rejected telegrams
[2] = Number of framing errors
[3] = Number of overrun errors
[4] = Number of parity errors
[5] = Number of starting character errors
[6] = Number of checksum errors
[7] = Number of length errors
Description:
Sets the baud rate for the fieldbus interface USS.
Value:
4:
2400 baud
5:
4800 baud
6:
9600 baud
7:
19200 baud
8:
38400 baud
9:
57600 baud
10:
76800 baud
11:
93750 baud
12:
115200 baud
13:
187500 baud
Note:
Fieldbus IF: Fieldbus interface
Changes only become effective after POWER ON.
The parameter is not influenced by setting the factory setting.
The parameter is set to the factory setting when the protocol is reselected.
Description:
Sets the address for the fieldbus interface USS.
Dependency:
Refer to: p2030
p2011
Comm IF address / Comm add
CU_DCP
Can be changed:
T
Access level:
2
Data type:
Unsigned16
Func. diagram:
-
Min Max
Factory
setting
1 127
3
r2019[0...7]
Comm IF error statistics / Comm err
CU_DCP
Can be changed:
-
Access level:
4
Data type:
Unsigned32
Func. diagram:
-
Min Max
Factory
setting
- -
-
p2020
Field bus interface baud rate / Field bus baud
CU_DCP
Can be changed:
T
Access level:
2
Data type:
Integer16
Func. diagram:
9310
Min Max
Factory
setting
4 13
8
p2021
Field bus interface address / Field bus address
CU_DCP
Can be changed:
T
Access level:
2
Data type:
Unsigned16
Func. diagram:
-
Min Max
Factory
setting
0 31
0
Summary of Contents for sinamics dcp
Page 2: ......
Page 6: ...Preface SINAMICS DCP 6 List Manual LH21 05 2016 ...
Page 8: ...Table of contents SINAMICS DCP 8 List Manual LH21 05 2016 ...
Page 510: ...A Appendix A 2 List of abbreviations SINAMICS DCP 510 List Manual LH21 05 2016 ...
Page 516: ...Index SINAMICS DCP 516 List Manual LH21 05 2016 ...
Page 517: ...Siemens Parts ...