SINAMICS DCP
List Manual (LH21), 05/2016
495
4 Faults and alarms
4.2 List of faults and alarms
F60509 (N, A)
Power unit undervoltage
Drive object:
DCP_CTRL
Cause:
In operation, the input voltage or output voltage has fallen below 30 V.
Fault value (r0949, interpret decimal):
1: Undervoltage on side 1.
2: Undervoltage on side 2.
Remedy:
Check the input voltage (side 1) and/or output voltage (side 2).
A60510 (F, N)
Device fan service life reached
Drive object:
DCP_CTRL
Cause:
The device fan has reached its set service life in 500 hours.
The service life of the device fan is set in p55471.
Remedy:
Replace the device fan and reset the operating hours counter.
Procedure to reset the operating hours:
Set p55472 = 1
--> the operating hours counter (r55470) is set to zero.
--> the parameter is automatically set to zero after this is done.
See also: r55470 (Device fan operating hours display), p55471 (Device fan service life), p55472 (Device fan reset
operating hours)
F60511 (N, A)
Deviation between the internal and external current actual value too high
Drive object:
DCP_CTRL
Cause:
The deviation between the internal and external current actual value is too high.
Note:
The signal source for the external current actual value was set in p55156.
Remedy:
- check the external current transformer for the current actual value.
- if necessary increase the threshold to identify the deviation (p55161).
See also: p55161 (Correction current controller limiting)
A60520 (F, N)
Alarm module temperature exceeded
Drive object:
DCP_CTRL
Cause:
The temperature has exceeded 90 °C.
Fault value (r0949, interpret decimal):
3: Power supply module temperature too high.
4: Mainboard module temperature too high.
Note:
r50047[1]: Temperature power unit 1 (in °C)
r50047[2]: Temperature power unit 2 (in °C)
r50047[3]: Temperature power supply module (in °C)
r50047[4]: Temperature mainboard module (in °C)
r50047[5]: Temperature CUD module (in °C)
r50047[6]: Air intake temperature (in °C)
r50047[7]: Reference v10 V (in Volt)
r50047[8]: Reference voltage -10 V (in Volt)
r50047[9]: Temperature power unit 3 (in °C)
Remedy:
- check the ambient temperature and reduce if necessary.
- check the function of the device fan.
F60521 (N, A)
Fault module temperature exceeded
Drive object:
DCP_CTRL
Cause:
The temperature has exceeded 95 °C.
Fault value (r0949, interpret decimal):
3: Power supply module temperature too high.
4: Mainboard module temperature too high.
Summary of Contents for sinamics dcp
Page 2: ......
Page 6: ...Preface SINAMICS DCP 6 List Manual LH21 05 2016 ...
Page 8: ...Table of contents SINAMICS DCP 8 List Manual LH21 05 2016 ...
Page 510: ...A Appendix A 2 List of abbreviations SINAMICS DCP 510 List Manual LH21 05 2016 ...
Page 516: ...Index SINAMICS DCP 516 List Manual LH21 05 2016 ...
Page 517: ...Siemens Parts ...