SINAMICS DCP
List Manual (LH21), 05/2016
35
2 Parameters
2.2 List of parameters
Note:
Re value = 0, 2:
When a drive object is deactivated it no longer outputs any errors.
If value = 0:
All components of the drive object were completely commissioned and are deactivated using this value. They can be
removed from the DRIVE-CLiQ without any error.
If a component has been deactivated, only the component with the correct serial number may be inserted, or none at
all.
If value = 1:
All components of the drive object must be available for error-free operation.
If value = 2:
Components of a drive object in a project generated offline and set to this value must never be inserted in the actual
topology from the very start. This means that the components are marked to be bypassed in the DRIVE-CLiQ line.
For components that comprise several individual components (e.g. Double Motor Modules), it is not permissible to
set just one subset to this value.
Description:
Displays the "active/inactive" state of a drive object.
Value:
0:
Drive object inactive
1:
Drive object active
Dependency:
Refer to: p0105
Description:
The type of an existing drive object is entered into each index.
Value:
0:
-
1:
SINAMICS S
2:
SINAMICS G
3:
SINAMICS I
4:
SINAMICS NX/CX32
6:
SINAMICS DC
9:
SINAMICS S110
10:
ACTIVE INFEED CONTROL
11:
SERVO
12:
VECTOR
13:
VECTORMV
14:
VECTORGL
15:
VECTOR3P
16:
VECTORSL
17:
DC_CTRL
18:
VECTORM2C
19:
VECTORDM
20:
SMART INFEED CONTROL
21:
RENEWABLE INFEED CONTROL
30:
BASIC INFEED CONTROL
35:
BRAKE MODULE M2C
40:
ACTIVE INFEED CONTROLMV
41:
BASIC INFEED CONTROLMV
42:
ACTIVE INFEED CONTROLM2C
51:
SINAMICS G120 230 (SingleDO-Drive which combines Vector)
52:
SINAMICSG120 240_2 (SingleDO-Drive which combines Vector)
53:
SINAMICS_G120_CU250S_V (SingleDO Drive combines Vector)
54:
SINAMICSG120 G120D(SingleDO-Drive which combines Vector)
55:
SINAMICS_G120_CU250S_S (SingleDO Drive combines Servo)
r0106
Drive object active/inactive / DO act/inact
All objects
Can be changed:
-
Access level:
2
Data type:
Integer16
Func. diagram:
-
Min Max
Factory
setting
0 1
-
p0107[0...n]
Drive object type / DO type
CU_DCP
Can be changed:
C1(2)
Access level:
2
Data type:
Integer16
Func. diagram:
-
Min Max
Factory
setting
0 600
0
Summary of Contents for sinamics dcp
Page 2: ......
Page 6: ...Preface SINAMICS DCP 6 List Manual LH21 05 2016 ...
Page 8: ...Table of contents SINAMICS DCP 8 List Manual LH21 05 2016 ...
Page 510: ...A Appendix A 2 List of abbreviations SINAMICS DCP 510 List Manual LH21 05 2016 ...
Page 516: ...Index SINAMICS DCP 516 List Manual LH21 05 2016 ...
Page 517: ...Siemens Parts ...