2 Parameters
2.2 List of parameters
SINAMICS DCP
86
List Manual (LH21), 05/2016
395:
SIEMENS telegram 395, PZD-4/25
396:
SIEMENS telegram 396, PZD-20/21
999:
Free telegram configuration with BICO
Note:
For p0922 < 999 the following applies:
p2079 has the same value and is inhibited. All of the interconnections and extensions contained in the telegram are
inhibited.
For p0922 = 999 the following applies:
p2079 can be freely set. If p2079 is also set to 999, then all of the interconnections can be set.
For p0922 = 999 and p2079 < 999 the following applies:
The interconnections contained in the telegram are inhibited. However, the telegram can be extended.
Description:
Sets the send and receive telegram.
Contrary to p0922, a telegram can be selected using p2079 and subsequently expanded.
Value:
1:
Standard telegram 1, PZD-2/2
3:
Standard telegram 3, PZD-5/9
4:
Standard telegram 4, PZD-6/14
20:
Standard telegram 20, PZD-2/6
220:
SIEMENS telegram 220, PZD-10/10
352:
SIEMENS telegram 352, PZD-6/6
999:
Free telegram configuration with BICO
Dependency:
Refer to: p0922
Note:
For p0922 < 999 the following applies:
p2079 has the same value and is inhibited. All of the interconnections and extensions contained in the telegram are
inhibited.
For p0922 = 999 the following applies:
p2079 can be freely set. If p2079 is also set to 999, then all of the interconnections can be set.
For p0922 = 999 and p2079 < 999 the following applies:
The interconnections contained in the telegram are inhibited. However, the telegram can be extended.
Description:
Selects bits to be sent to the PROFIdrive controller.
The individual bits are combined to form status word 1.
Index:
[0] = Bit 0
[1] = Bit 1
[2] = Bit 2
[3] = Bit 3
[4] = Bit 4
[5] = Bit 5
[6] = Bit 6
[7] = Bit 7
[8] = Bit 8
[9] = Bit 9
[10] = Bit 10
[11] = Bit 11
[12] = Bit 12
[13] = Bit 13
[14] = Bit 14
[15] = Bit 15
Dependency:
Refer to: p2088, r2089
p2079
IF1 PROFIdrive PZD telegram selection extended / IF1 PZD telegr ext
DCP_CTRL
Can be changed:
T
Access level:
3
Data type:
Integer16
Func. diagram:
-
Min Max
Factory
setting
1 999
999
p2080[0...15]
BI: Binector-connector converter status word 1 / Bin/con ZSW1
All objects
Can be changed:
U, T
Access level:
3
Data type:
Unsigned32 / Binary
Func. diagram:
2472
Min Max
Factory
setting
- -
0
Summary of Contents for sinamics dcp
Page 2: ......
Page 6: ...Preface SINAMICS DCP 6 List Manual LH21 05 2016 ...
Page 8: ...Table of contents SINAMICS DCP 8 List Manual LH21 05 2016 ...
Page 510: ...A Appendix A 2 List of abbreviations SINAMICS DCP 510 List Manual LH21 05 2016 ...
Page 516: ...Index SINAMICS DCP 516 List Manual LH21 05 2016 ...
Page 517: ...Siemens Parts ...