SINAMICS DCP
List Manual (LH21), 05/2016
123
2 Parameters
2.2 List of parameters
Description:
Displays the counter reading for modified BICO interconnections on this drive object.
The counter is incremented by one for each modified BICO interconnection.
Description:
Setting to acknowledge all active faults of a drive object.
Notice:
Safety messages cannot be acknowledged using this parameter.
Note:
Parameter should be set from 0 to 1 to acknowledge.
After acknowledgement, the parameter is automatically reset to 0.
Description:
Sets the mode to change over the master control / LOCAL mode.
Value:
0:
Change master control for STW1.0 = 0
1:
Change master control in operation
Danger:
When changing the master control in operation, the drive can manifest undesirable behavior - e.g. it can accelerate
up to another setpoint.
Description:
Displays the number of parameters for this drive unit.
The number comprises the device-specific and the drive-specific parameters.
Dependency:
Refer to: r0980, r0981, r0989
Description:
Index 0:
Displays the boot state.
Index 1:
Displays the partial boot state
Value:
0:
Not active
1:
Fatal fault
10:
Fault
20:
Reset all parameters
30:
Drive object modified
40:
Download using commissioning software
r3979
BICO counter drive object / BICO counter DO
DCP_CTRL, TM150,
TM15DI_DO, TM31
Can be changed:
-
Access level:
4
Data type:
Unsigned32
Func. diagram:
-
Min Max
Factory
setting
- -
-
p3981
Faults acknowledge drive object / Faults ackn DO
All objects
Can be changed:
U, T
Access level:
2
Data type:
Unsigned8
Func. diagram:
8060
Min Max
Factory
setting
0 1
0
p3985
Master control mode selection / PcCtrl mode select
DCP_CTRL
Can be changed:
U, T
Access level:
3
Data type:
Integer16
Func. diagram:
-
Min Max
Factory
setting
0 1
0
r3986
Parameter count / Parameter No.
All objects
Can be changed:
-
Access level:
3
Data type:
Unsigned16
Func. diagram:
-
Min Max
Factory
setting
- -
-
r3988[0...1]
Boot state / Boot_state
CU_DCP
Can be changed:
-
Access level:
3
Data type:
Integer16
Func. diagram:
-
Min Max
Factory
setting
0 10800
-
Summary of Contents for sinamics dcp
Page 2: ......
Page 6: ...Preface SINAMICS DCP 6 List Manual LH21 05 2016 ...
Page 8: ...Table of contents SINAMICS DCP 8 List Manual LH21 05 2016 ...
Page 510: ...A Appendix A 2 List of abbreviations SINAMICS DCP 510 List Manual LH21 05 2016 ...
Page 516: ...Index SINAMICS DCP 516 List Manual LH21 05 2016 ...
Page 517: ...Siemens Parts ...