SINAMICS DCP
List Manual (LH21), 05/2016
483
4 Faults and alarms
4.2 List of faults and alarms
A50003 (F)
COMM BOARD: Alarm 3
Drive object:
CU_DCP, TM150, TM15DI_DO, TM31
Cause:
CBE20 SINAMICS Link:
A specific telegram word (receive) is being used twice.
Alarm value (r2124, interpret hexadecimal):
yyyyxxxx hex: yyyy = info. 1, xxxx = info. 2
Info. 1 (decimal) = Address of sender
Info. 2 (decimal) = Receive telegram word
See also: p8870 (SINAMICS Link receive telegram word PZD), p8872 (SINAMICS Link address receive PZD)
Remedy:
CBE20 SINAMICS Link:
Correct the parameter assignment.
A50004 (F)
COMM BOARD: Alarm 4
Drive object:
CU_DCP, TM150, TM15DI_DO, TM31
Cause:
CBE20 SINAMICS Link:
- telegram word (receive) and address of sender inconsistent. Both values have to be either equal to zero or not
equal to zero.
- drive object number p8872 > 16 with p8811 = 16.
Alarm value (r2124, interpret hexadecimal):
yyyyxxxx hex: yyyy = info. 1, xxxx = info. 2
Info. 1 (decimal) = Drive object number from p8870, p8872
Info. 2 (decimal) = Index from p8870, p8872
See also: p8870 (SINAMICS Link receive telegram word PZD), p8872 (SINAMICS Link address receive PZD)
Remedy:
In the case of CBE20 SINAMICS Link:
Correct the parameter assignment.
A50005 (F)
COMM BOARD: Alarm 5
Drive object:
CU_DCP, TM150, TM15DI_DO, TM31
Cause:
CBE20 SINAMICS Link:
Sender not found on SINAMICS Link.
Alarm value (r2124, interpret decimal):
Address of sender that cannot be located
See also: p8872 (SINAMICS Link address receive PZD)
Remedy:
CBE20 SINAMICS Link:
Check the connection to the sender.
A50006 (F)
COMM BOARD: Alarm 6
Drive object:
CU_DCP, TM150, TM15DI_DO, TM31
Cause:
CBE20 SINAMICS Link:
The parameter assignment indicates that the sender and the receiver are one and the same. This is not permitted.
Alarm value (r2124, interpret hexadecimal):
yyyyxxxx hex: yyyy = info. 1, xxxx = info. 2
Info. 1 (decimal) = Drive object number from p8872
Info. 2 (decimal) = Index from p8872
See also: p8872 (SINAMICS Link address receive PZD)
Remedy:
In the case of CBE20 SINAMICS Link:
Correct the parameter assignment. All p8872[index] must be set to a value not equal to p8836.
A50010 (F)
PN/COMM BOARD: Station name invalid
Drive object:
All objects
Cause:
CBE20:
PROFINET Name of Station is invalid.
Remedy:
CBE20:
Correct the name of the station (p8940) and activate (p8945 = 2).
See also: p8940 (CBE2x Name of Station)
Summary of Contents for sinamics dcp
Page 2: ......
Page 6: ...Preface SINAMICS DCP 6 List Manual LH21 05 2016 ...
Page 8: ...Table of contents SINAMICS DCP 8 List Manual LH21 05 2016 ...
Page 510: ...A Appendix A 2 List of abbreviations SINAMICS DCP 510 List Manual LH21 05 2016 ...
Page 516: ...Index SINAMICS DCP 516 List Manual LH21 05 2016 ...
Page 517: ...Siemens Parts ...