4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
404
List Manual (LH21), 05/2016
For fault value = 208:
Check parameter p0430.23 and reset if necessary.
A01304 (F)
Firmware version of DRIVE-CLiQ component is not up-to-date
Drive object:
CU_DCP, TM150, TM15DI_DO, TM31
Cause:
The non-volatile memory has a more recent firmware version than the one in the connected DRIVE-CLiQ
component.
Alarm value (r2124, interpret decimal):
Component number of the DRIVE-CLiQ component involved.
Remedy:
Update the firmware (p7828, p7829 and commissioning software).
F01305
Topology: Component number missing
Drive object:
CU_DCP, TM150, TM15DI_DO, TM31
Cause:
The component number from the topology was not parameterized (p0121 (for power unit, refer to p0107), p0131 (for
servo/vector drives, refer to p0107), p0141, p0151, p0161).
Fault value (r0949, interpret decimal):
Data set number.
Note:
The fault also occurs if encoders have been configured (p0187 to p0189) but no component numbers exist for them.
In this case, the fault value includes the drive data set number plus 100 * encoder number (e.g. 3xx, if a component
number was not entered in p0141 for encoder 3 (p0189)).
See also: p0151 (Terminal Module component number)
Remedy:
- enter missing component number.
- if required, remove the component and restart commissioning.
See also: p0151 (Terminal Module component number)
A01306
Firmware of the DRIVE-CLiQ component being updated
Drive object:
CU_DCP, TM150, TM15DI_DO, TM31
Cause:
Firmware update is active for at least one DRIVE-CLiQ component.
Alarm value (r2124, interpret decimal):
Component number of the DRIVE-CLiQ component.
Remedy:
Not necessary.
This alarm automatically disappears after the firmware has been updated.
A01314
Topology: Component must not be present
Drive object:
TM150, TM15DI_DO, TM31
Cause:
For a component, "de-activate and not present" is set but this component is still in the topology.
Alarm value (r2124, interpret hexadecimal):
ddccbbaa hex:
aa = component number
bb = component class of the component
cc = connection number
Note:
Component class and connection number are described in F01375.
Remedy:
- remove the corresponding component.
- change the setting "de-activate and not present".
Note:
Under "Topology --> Topology view" the commissioning software where relevant offers improved diagnostics
capability (e.g. setpoint/actual value comparison).
See also: p0105 (Activate/de-activate drive object)
A01315
Drive object not ready for operation
Drive object:
CU_DCP, TM150, TM15DI_DO, TM31
Cause:
For the active drive object involved, at least one activated component is missing.
Note:
All other active and operational drive objects can be in the "RUN" state.
Summary of Contents for sinamics dcp
Page 2: ......
Page 6: ...Preface SINAMICS DCP 6 List Manual LH21 05 2016 ...
Page 8: ...Table of contents SINAMICS DCP 8 List Manual LH21 05 2016 ...
Page 510: ...A Appendix A 2 List of abbreviations SINAMICS DCP 510 List Manual LH21 05 2016 ...
Page 516: ...Index SINAMICS DCP 516 List Manual LH21 05 2016 ...
Page 517: ...Siemens Parts ...