SINAMICS DCP
List Manual (LH21), 05/2016
283
2 Parameters
2.2 List of parameters
If value = 12:
The current at side 2 is specified as setpoint.
If U1 <= U2: reactor current setpoint = setpoint * U2/U1
If U1 > U2: reactor current setpoint = setpoint (no conversion)
If value = 20:
The power is specified as setpoint.
If U1 <= U2: reactor current setpoint = setpoint/U1
If U1 > U2: reactor current setpoint = setpoint/U2
Explanation:
U1: voltage at side 1
U2: voltage at side 2
All values are referred to rated device quantities (rated current, rated voltage, rated power).
Description:
Sets the delay time for the current direction change.
The delay time is started when the sign changes at the ramp-function generator output.
A current setpoint of zero is entered while the delay time is running.
Description:
Display and connector output for the current setpoint after the ramp-function generator.
Description:
Display and connector output for the current setpoint in the reactor.
Description:
Display and connector output for the current setpoint after suppressing low setpoints.
Description:
Display and connector output for the current setpoint after the correction current controller.
p55065
Current setpoint sign delay time / I_set sign t_del
DCP_CTRL
Can be changed:
U, T
Access level:
2
Data type:
FloatingPoint32
Func. diagram:
6805
Min Max
Factory
setting
0.250 [ms]
1000.000 [ms]
100.000 [ms]
r55070
CO: Current setpoint after the ramp-function generator / I_set after RFG
DCP_CTRL
Can be changed:
-
Access level:
2
Data type:
FloatingPoint32
Func. diagram:
6805
Min Max
Factory
setting
- [%]
- [%]
- [%]
r55071
CO: Current setpoint reactor / I_set reactor
DCP_CTRL
Can be changed:
-
Access level:
2
Data type:
FloatingPoint32
Func. diagram:
6806
Min Max
Factory
setting
- [%]
- [%]
- [%]
r55072
CO: Current setpoint after limiting to the minimum / I_set aft lim min
DCP_CTRL
Can be changed:
-
Access level:
2
Data type:
FloatingPoint32
Func. diagram:
6805
Min Max
Factory
setting
- [%]
- [%]
- [%]
r55073
CO: Current setpoint corrected / I_set corrected
DCP_CTRL
Can be changed:
-
Access level:
2
Data type:
FloatingPoint32
Func. diagram:
6806
Min Max
Factory
setting
- [%]
- [%]
- [%]
Summary of Contents for sinamics dcp
Page 2: ......
Page 6: ...Preface SINAMICS DCP 6 List Manual LH21 05 2016 ...
Page 8: ...Table of contents SINAMICS DCP 8 List Manual LH21 05 2016 ...
Page 510: ...A Appendix A 2 List of abbreviations SINAMICS DCP 510 List Manual LH21 05 2016 ...
Page 516: ...Index SINAMICS DCP 516 List Manual LH21 05 2016 ...
Page 517: ...Siemens Parts ...