2 Parameters
2.2 List of parameters
SINAMICS DCP
148
List Manual (LH21), 05/2016
Note:
The changed sampling time is immediately effective after a completed sub-boot (p0009 -> 0).
Parameter p4099[0] must never be equal to zero.
Description:
Sets the sensor type for Terminal Module 150 (TM150)
This means that the temperature sensor type is selected and the evaluation is switched in.
Value:
0:
Evaluation disabled
1:
PTC thermistor
2:
KTY84
4:
Bimetallic NC contact
5:
PT100
6:
PT1000
Index:
[0] = Temperature channel 0
[1] = Temperature channel 1
[2] = Temperature channel 2
[3] = Temperature channel 3
[4] = Temperature channel 4
[5] = Temperature channel 5
[6] = Temperature channel 6
[7] = Temperature channel 7
[8] = Temperature channel 8
[9] = Temperature channel 9
[10] = Temperature channel 10
[11] = Temperature channel 11
Notice:
For p4102[0...23] = 251 °C, evaluation of the corresponding threshold is deactivated.
For sensor type "PTC thermistor" and "Bimetallic NC contact" (p4100[0...11] = 1, 4), the following applies:
To activate the corresponding alarm or fault, p4102[0...23] must be set <= 250 °C.
Note:
The temperature sensors are connected to the following terminals:
X531 = channel 0 (for 2x2 wire evaluation, additionally channel 6)
X532 = channel 1 (for 2x2 wire evaluation, additionally channel 7)
X533 = channel 2 (for 2x2 wire evaluation, additionally channel 8)
X534 = channel 3 (for 2x2 wire evaluation, additionally channel 9)
X535 = channel 4 (for 2x2 wire evaluation, additionally channel 10)
X536 = channel 5 (for 2x2 wire evaluation, additionally channel 11)
Details on the wiring are included in the parameter description for p4108.
Description:
Sets the sensor type for Terminal Module 31 (TM31)
This means that the temperature sensor type is selected and the evaluation is switched in.
Value:
0:
Evaluation disabled
1:
PTC thermistor
2:
KTY84
Notice:
For p4102[0...1] = 251 °C, evaluation of the corresponding threshold is deactivated.
For sensor type "PTC thermistor" (p4100 = 1), the following applies:
To activate the corresponding alarm or fault, p4102[0...1] must be set <= 250 °C.
Note:
The temperature sensor is connected at terminals X522.7(+) and X522.8(-).
p4100[0...11]
TM150 sensor type / TM150 sensor type
TM150
Can be changed:
T
Access level:
1
Data type:
Integer16
Func. diagram:
9626, 9627
Min Max
Factory
setting
0 6
5
p4100
TM31 sensor type / TM31 sensor type
TM31
Can be changed:
T
Access level:
1
Data type:
Integer16
Func. diagram:
9576
Min Max
Factory
setting
0 2
0
Summary of Contents for sinamics dcp
Page 2: ......
Page 6: ...Preface SINAMICS DCP 6 List Manual LH21 05 2016 ...
Page 8: ...Table of contents SINAMICS DCP 8 List Manual LH21 05 2016 ...
Page 510: ...A Appendix A 2 List of abbreviations SINAMICS DCP 510 List Manual LH21 05 2016 ...
Page 516: ...Index SINAMICS DCP 516 List Manual LH21 05 2016 ...
Page 517: ...Siemens Parts ...