![Siemens sinamics dcp Manual Download Page 107](http://html.mh-extra.com/html/siemens/sinamics-dcp/sinamics-dcp_manual_381559107.webp)
SINAMICS DCP
List Manual (LH21), 05/2016
107
2 Parameters
2.2 List of parameters
Dependency:
Selects the faults and sets the required acknowledge mode realized under the same index
Refer to: p2127
Note:
Re-parameterization is also possible if a fault is present. The change only becomes effective after the fault has been
resolved.
Description:
Selects the faults for which the acknowledge mode is to be changed
Dependency:
Selects the faults and sets the required acknowledge mode realized under the same index
Refer to: p2127
Note:
Re-parameterization is also possible if a fault is present. The change only becomes effective after the fault has been
resolved.
Description:
Sets the acknowledge mode for selected fault.
Value:
1:
Acknowledgment only using POWER ON
2:
Ack IMMEDIATELY after the fault cause has been removed
3:
Acknowledgement only for PULSE INHIBIT
Dependency:
Selects the faults and sets the required acknowledge mode realized under the same index
Refer to: p2126
Notice:
It is not possible to re-parameterize the acknowledge mode for a fault in the following cases:
- Fault number does not exist (exception value = 0).
- Message type is not "fault" (F).
- Acknowledge mode is not permissible for the set fault number.
Note:
Re-parameterization is also possible if a fault is present. The change only becomes effective after the fault has been
resolved.
The acknowledge mode can only be changed for faults with the appropriate identification.
Example:
F12345 and acknowledge mode = IMMEDIATELY (POWER ON)
--> The acknowledge mode can be changed from IMMEDIATELY to POWER ON.
Description:
Sets the acknowledge mode for selected fault.
Value:
1:
Acknowledgment only using POWER ON
2:
Ack IMMEDIATELY after the fault cause has been removed
3:
Acknowledgement only for PULSE INHIBIT
Dependency:
Selects the faults and sets the required acknowledge mode realized under the same index
Refer to: p2126
Notice:
It is not possible to re-parameterize the acknowledge mode for a fault in the following cases:
- Fault number does not exist (exception value = 0).
- Message type is not "fault" (F).
- Acknowledge mode is not permissible for the set fault number.
p2126[0...19]
Change acknowledge mode fault number / Chng ackn F_no
TM150, TM15DI_DO,
TM31
Can be changed:
U, T
Access level:
3
Data type:
Unsigned16
Func. diagram:
8050, 8075
Min Max
Factory
setting
0 65535
0
p2127[0...19]
Change acknowledge mode mode / Chng ackn mode
CU_DCP, DCP_CTRL
Can be changed:
U, T
Access level:
3
Data type:
Integer16
Func. diagram:
8075
Min Max
Factory
setting
1 3
1
p2127[0...19]
Change acknowledge mode mode / Chng ackn mode
TM150, TM15DI_DO,
TM31
Can be changed:
U, T
Access level:
3
Data type:
Integer16
Func. diagram:
8050, 8075
Min Max
Factory
setting
1 3
1
Summary of Contents for sinamics dcp
Page 2: ......
Page 6: ...Preface SINAMICS DCP 6 List Manual LH21 05 2016 ...
Page 8: ...Table of contents SINAMICS DCP 8 List Manual LH21 05 2016 ...
Page 510: ...A Appendix A 2 List of abbreviations SINAMICS DCP 510 List Manual LH21 05 2016 ...
Page 516: ...Index SINAMICS DCP 516 List Manual LH21 05 2016 ...
Page 517: ...Siemens Parts ...