2 Parameters
2.2 List of parameters
SINAMICS DCP
56
List Manual (LH21), 05/2016
Description:
The parameter is used to initiate a reset of the parameters on Terminal Module 15 (TM15).
The sampling time p4099 is not reset if in so doing a conflict occurs with the basic clock cycle.
Parameter p0151 is not reset. It is only reset if the entire drive unit is reset to the factory settings (p0976).
Value:
0:
Inactive
1:
Start a parameter reset
100:
Start a BICO interconnection reset
Dependency:
Refer to: p0010
Notice:
After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
Note:
A factory setting run can only be started if p0010 was first set to 30 (parameter reset).
At the end of the calculations, p0970 is automatically set to 0.
Description:
The parameter is used to initiate a reset of the parameters on Terminal Module 31 (TM31).
The sampling time p4099 is not reset if in so doing a conflict occurs with the basic clock cycle.
Parameter p0151 is not reset. It is only reset if the entire drive unit is reset to the factory settings (p0976).
Value:
0:
Inactive
1:
Start a parameter reset
100:
Start a BICO interconnection reset
Dependency:
Refer to: p0010
Notice:
After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
Note:
A factory setting run can only be started if p0010 was first set to 30 (parameter reset).
At the end of the calculations, p0970 is automatically set to 0.
Description:
Setting to save the parameter of the particular drive object in the non-volatile memory.
When saving, only the adjustable parameters intended to be saved are taken into account.
Value:
0:
Inactive
1:
Save drive object
Dependency:
Refer to: p0977, r3996
Caution:
If a memory card (optional) is inserted, the following applies:
The parameters are also saved on the card and therefore overwrite any existing data!
Notice:
The Control Unit power supply may only be powered down after data has been saved (i.e. after data save has been
started, wait until the parameter again has the value 0).
Writing to parameters is inhibited while saving.
The progress while saving is displayed in r3996.
p0970
TM15DI/DO reset parameter / TM15D par reset
TM15DI_DO
Can be changed:
C2(30)
Access level:
2
Data type:
Unsigned16
Func. diagram:
-
Min Max
Factory
setting
0 100
0
p0970
TM31 reset parameters / TM31 par reset
TM31
Can be changed:
C2(30)
Access level:
2
Data type:
Unsigned16
Func. diagram:
-
Min Max
Factory
setting
0 100
0
p0971
Save drive object parameters / Drv_obj par save
CU_DCP, DCP_CTRL
Can be changed:
U, T
Access level:
1
Data type:
Unsigned16
Func. diagram:
-
Min Max
Factory
setting
0 1
0
Summary of Contents for sinamics dcp
Page 2: ......
Page 6: ...Preface SINAMICS DCP 6 List Manual LH21 05 2016 ...
Page 8: ...Table of contents SINAMICS DCP 8 List Manual LH21 05 2016 ...
Page 510: ...A Appendix A 2 List of abbreviations SINAMICS DCP 510 List Manual LH21 05 2016 ...
Page 516: ...Index SINAMICS DCP 516 List Manual LH21 05 2016 ...
Page 517: ...Siemens Parts ...