2 Parameters
2.2 List of parameters
SINAMICS DCP
50
List Manual (LH21), 05/2016
Description:
Display and connector output for the control word of the sequence control.
Note:
OC: Operating condition
Description:
Displays the status word of the sequence control.
Note:
Re bits 00, 01, 02, 04, 05, 06, 09:
For PROFIdrive, these signals are used for status word 1.
Description:
Sets the PROFIBUS address for PROFIBUS interface (X126) on the Control Unit.
r0898.0...14
CO/BO: Control word sequence control / STW seq_ctrl
DCP_CTRL
Can be changed:
-
Access level:
2
Data type:
Unsigned16
Func. diagram:
2580
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
ON/OFF1
Yes
No
-
01
OC / OFF2
Yes
No
-
02
OC / OFF3
Yes
No
-
03
Operation enable
Yes
No
-
04
Ramp-function generator enable
Yes
No
-
05
Continue ramp-function generator
Yes
No
-
06
Speed setpoint enable
Yes
No
-
07
Command open brake
Yes
No
-
08
Jog 1
Yes
No
-
09
Jog 2
Yes
No
-
10
Master ctrl by PLC
Yes
No
-
12
Speed controller enable
Yes
No
-
14
Command close brake
Yes
No
-
r0899.0...15
CO/BO: Status word sequence control / ZSW seq_ctrl
DCP_CTRL
Can be changed:
-
Access level:
2
Data type:
Unsigned16
Func. diagram:
2585, 2750,
3150, 3151, 3152, 6810, 6830
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Rdy for switch on
Yes
No
-
01
Ready
Yes
No
-
02
Operation enabled
Yes
No
-
03
Jog active
Yes
No
-
04
No coasting active
OFF2 inactive
OFF2 active
-
05
No Quick Stop active
OFF3 inactive
OFF3 active
-
06
Switching on inhibited active
Yes
No
-
07
Drive ready
Yes
No
-
08
Controller enable
Yes
No
-
09
Control request
Yes
No
-
11
Pulses enabled
Yes
No
-
12
Open holding brake
Yes
No
-
13
Command close holding brake
Yes
No
-
14
Pulse enable from the brake control
Yes
No
-
15
Setpoint enable from the brake control
Yes
No
-
p0918
PROFIBUS address / PB address
CU_DCP
Can be changed:
T
Access level:
2
Data type:
Unsigned16
Func. diagram:
1520, 2410
Min Max
Factory
setting
1 126
126
Summary of Contents for sinamics dcp
Page 2: ......
Page 6: ...Preface SINAMICS DCP 6 List Manual LH21 05 2016 ...
Page 8: ...Table of contents SINAMICS DCP 8 List Manual LH21 05 2016 ...
Page 510: ...A Appendix A 2 List of abbreviations SINAMICS DCP 510 List Manual LH21 05 2016 ...
Page 516: ...Index SINAMICS DCP 516 List Manual LH21 05 2016 ...
Page 517: ...Siemens Parts ...