4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
400
List Manual (LH21), 05/2016
64: DI/DO 8 (X122.7)
128: DI/DO 12 (X132.7)
Remedy:
Reduce the frequency of the pulses at the measuring probe input.
F01150
CU: Number of instances of a drive object type exceeded
Drive object:
All objects
Cause:
The maximum permissible number of instances of a drive object type was exceeded.
Drive object type:
Drive object type (p0107), for which the maximum permissible number of instances was exceeded.
Number permitted:
Max. permissible number of instances for this drive object type.
Actual number:
Current number of instances for this drive object type.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
ddccbbaa hex: aa = drive object type, bb = number limited, cc = actual number, dd = no significance
Remedy:
- power down the unit.
- suitably restrict the number of instances of a drive object type by reducing the number of inserted components.
- re-commission the unit.
F01151
CU: Number of drive objects of a category exceeded
Drive object:
All objects
Cause:
The maximum permissible number of drive objects of a category was exceeded.
Drive object category:
Drive object category, for which the maximum permissible number of drive objects was exceeded.
Number permitted:
Max. permissible number for this drive object category.
Actual number:
Actual number for this drive object category.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
ddccbbaa hex: aa = drive object category, bb = number limited, cc = actual number, dd = no significance
Remedy:
- power down the unit.
- suitably restrict the number of drive objects of the specified category by reducing the number of inserted
components.
- re-commission the unit.
F01152
CU: Invalid constellation of drive object types
Drive object:
All objects
Cause:
It is not possible to simultaneously operate drive object types SERVO, VECTOR and HLA.
A maximum of 2 of these drive object types can be operated on a Control Unit.
Remedy:
- power down the unit.
- restrict the use of drive object types SERVO, VECTOR, HLA to a maximum of 2.
- re-commission the unit.
F01200
CU: Time slice management internal software error
Drive object:
All objects
Cause:
A time slice management error has occurred.
It is possible that the sampling times have been inadmissibly set.
Fault value (r0949, interpret hexadecimal):
998:
Too many time slices occupied by OA (e.g. DCC).
999:
Too many time slices occupied by the basic system. Too many different sampling times may have been set.
Additional values:
Only for internal Siemens troubleshooting.
Summary of Contents for sinamics dcp
Page 2: ......
Page 6: ...Preface SINAMICS DCP 6 List Manual LH21 05 2016 ...
Page 8: ...Table of contents SINAMICS DCP 8 List Manual LH21 05 2016 ...
Page 510: ...A Appendix A 2 List of abbreviations SINAMICS DCP 510 List Manual LH21 05 2016 ...
Page 516: ...Index SINAMICS DCP 516 List Manual LH21 05 2016 ...
Page 517: ...Siemens Parts ...