SINAMICS DCP
List Manual (LH21), 05/2016
161
2 Parameters
2.2 List of parameters
Description:
Sets the trigger condition for the trace.
Value:
1:
Immediate trace start
2:
Positive edge
3:
Negative edge
4:
Entry to hysteresis band
5:
Leaving hysteresis band
6:
Trigger at bit mask
7:
Start with function generator
8:
Trigger at bit mask with edge
Index:
[0] = Trace 0
[1] = Trace 1
Description:
Selects the trigger signal for the trace.
Index:
[0] = Trace 0 parameter in BICO format
[1] = Trace 1 parameter in BICO format
[2] = Trace 0 PINx with DO Id and chart Id
[3] = Trace 0 PINx with block Id and PIN Id
[4] = Trace 1 PINy with DO Id and chart Id
[5] = Trace 1 PINy with block Id and PIN Id
Dependency:
Only effective when p4710 does not equal 1.
Note:
It only makes sense to trace the PINs using the commissioning software.
For index 2(4) and 3(5) equal to zero, index 0(1) can only be written and vice versa.
Re index 0 ... 1:
Here, the trigger signal for trace 0 or 1 is entered as parameter in the BICO format.
For trace with a physical address (p4789), the data type of the trigger signal is set here.
Re index 2 ...3:
The triggering PIN for trace 0 is entered here.
Index 2 bit 31 ... 16: Number of the Drive Object (DO), bit 15 ... 0: Number of the chart
Index 3 bit 31 ... 16: Number of the block, bit 15 ... 0: Number of the PIN
Re index 4 ... 5:
The triggering PIN for trace 1 is entered here.
Index 4 bit 31 ... 16: Number of the Drive Object (DO), bit 15 ... 0: Number of the chart
Index 5 bit 31 ... 16: Number of the block, bit 15 ... 0: Number of the PIN
Description:
Sets the trigger threshold for the trace.
Index:
[0] = Trace 0
[1] = Trace 1
Dependency:
Only effective when p4710 = 2, 3.
p4710[0...1]
Trace trigger condition / Trace Trig_cond
CU_DCP
Can be changed:
U, T
Access level:
3
Data type:
Integer16
Func. diagram:
-
Min Max
Factory
setting
1 8
2
p4711[0...5]
Trace trigger signal / Trace trig_signal
CU_DCP
Can be changed:
U, T
Access level:
3
Data type:
Unsigned32
Func. diagram:
-
Min Max
Factory
setting
- -
0
p4712[0...1]
Trace trigger threshold / Trace trig_thresh
CU_DCP
Can be changed:
U, T
Access level:
3
Data type:
FloatingPoint32
Func. diagram:
-
Min Max
Factory
setting
-340.28235E36 340.28235E36
0.00
Summary of Contents for sinamics dcp
Page 2: ......
Page 6: ...Preface SINAMICS DCP 6 List Manual LH21 05 2016 ...
Page 8: ...Table of contents SINAMICS DCP 8 List Manual LH21 05 2016 ...
Page 510: ...A Appendix A 2 List of abbreviations SINAMICS DCP 510 List Manual LH21 05 2016 ...
Page 516: ...Index SINAMICS DCP 516 List Manual LH21 05 2016 ...
Page 517: ...Siemens Parts ...