2 Parameters
2.2 List of parameters
SINAMICS DCP
34
List Manual (LH21), 05/2016
Description:
Setting to activate/de-activate a drive object.
Value:
0:
De-activate drive object
1:
Activate drive object
2:
Drive object de-activate and not present
Recommendation:
After inserting all of the components of a drive object, before activating, first wait for Alarm A01316.
Dependency:
When activating drive objects with the safety functions enabled, the following applies:
After reactivating, a warm restart (p0009 = 30, p0976 = 2, 3) or POWER ON should be carried out.
Refer to: r0106
Refer to: A01316
Notice:
The following applies when activating:
If components are inserted for the first time and the appropriate drive object is activated, then the drive system is
automatically booted. To do this, the pulses of all of the drive objects must be suppressed.
Note:
Re value = 0, 2:
When a drive object is deactivated it no longer outputs any errors.
If value = 0:
All components of the drive object were completely commissioned and are deactivated using this value. They can be
removed from the DRIVE-CLiQ without any error.
If a component has been deactivated, only the component with the correct serial number may be inserted, or none at
all.
If value = 1:
All components of the drive object must be available for error-free operation.
If value = 2:
Components of a drive object in a project generated offline and set to this value must never be inserted in the actual
topology from the very start. This means that the components are marked to be bypassed in the DRIVE-CLiQ line.
For components that comprise several individual components (e.g. Double Motor Modules), it is not permissible to
set just one subset to this value.
Description:
Setting to activate/de-activate a drive object.
Value:
0:
De-activate drive object
1:
Activate drive object
2:
Drive object de-activate and not present
Recommendation:
After inserting all of the components of a drive object, before activating, first wait for Alarm A01316.
Dependency:
Refer to: r0106
Refer to: A01316
Warning:
A drive that is moved by simulating the inputs of a Terminal Module is brought to a standstill while this parameter is
being changed over.
Notice:
The following applies when activating:
If components are inserted for the first time and the appropriate drive object is activated, then the drive system is
automatically booted. To do this, the pulses of all of the drive objects must be suppressed.
p0105
Activate/de-activate drive object / DO act/deact
TM150, TM15DI_DO
Can be changed:
T
Access level:
2
Data type:
Integer16
Func. diagram:
-
Min Max
Factory
setting
0 2
1
p0105
Activate/de-activate drive object / DO act/deact
TM31
Can be changed:
T
Access level:
2
Data type:
Integer16
Func. diagram:
-
Min Max
Factory
setting
0 2
1
Summary of Contents for sinamics dcp
Page 2: ......
Page 6: ...Preface SINAMICS DCP 6 List Manual LH21 05 2016 ...
Page 8: ...Table of contents SINAMICS DCP 8 List Manual LH21 05 2016 ...
Page 510: ...A Appendix A 2 List of abbreviations SINAMICS DCP 510 List Manual LH21 05 2016 ...
Page 516: ...Index SINAMICS DCP 516 List Manual LH21 05 2016 ...
Page 517: ...Siemens Parts ...