2 Parameters
2.2 List of parameters
SINAMICS DCP
248
List Manual (LH21), 05/2016
Description:
Sets the time constant for smoothing the signal from analog input 2 (AI 2, X177.29/30) on the CUD.
Note:
AI: Analog Input
Description:
Sets the signal source to enable analog input 2 (AI 2, X177.29/30) on the CUD.
Note:
AI: Analog Input
Description:
Sets the scaling for fast analog inputs "Select input 3 ... 6".
The value indicates the percentage value for mapping an input voltage of 10 V at the analog input.
Example:
p50731[2] = 90%
--> 10 V is scaled to 90% for select input 5
--> 5 V corresponds to 45% for select input 5
Index:
[0] = Select input 3 (X177.1/2)
[1] = Select input 4 (X177.3/4)
[2] = Select input 5 (X177.5/6)
[3] = Select input 6 (X177.7/8)
Note:
AI: Analog Input
Description:
Sets the offset for fast analog inputs "Select input 3 ... 6".
Index:
[0] = Select input 3 (X177.1/2)
[1] = Select input 4 (X177.3/4)
[2] = Select input 5 (X177.5/6)
[3] = Select input 6 (X177.7/8)
Note:
AI: Analog Input
Description:
Sets the signal processing for fast analog inputs "Select input 3 ... 6".
p50725
CUD analog input 2 smoothing time constant / CUD AI 2 T
DCP_CTRL
Can be changed:
U, T
Access level:
3
Data type:
FloatingPoint32
Func. diagram:
2080
Min Max
Factory
setting
0 [ms]
10000 [ms]
0 [ms]
p50726
BI: CUD analog input 2 signal source for enable / CUD AI 2 ena s_src
DCP_CTRL
Can be changed:
T
Access level:
3
Data type:
Unsigned32 / Binary
Func. diagram:
2080
Min Max
Factory
setting
- -
1
p50731[0...3]
Fast analog inputs scaling / Fast AI scal
DCP_CTRL
Can be changed:
U, T
Access level:
3
Data type:
FloatingPoint32
Func. diagram:
2085, 2090
Min Max
Factory
setting
-1000.0 [%]
1000.0 [%]
100.0 [%]
p50732[0...3]
Fast analog inputs offset / Fast AI offs
DCP_CTRL
Can be changed:
U, T
Access level:
3
Data type:
FloatingPoint32
Func. diagram:
2085, 2090
Min Max
Factory
setting
-200.00 [%]
200.00 [%]
0.00 [%]
p50733[0...3]
Fast analog inputs signal processing / Fast AI sig
DCP_CTRL
Can be changed:
T
Access level:
3
Data type:
Integer16
Func. diagram:
2085, 2090
Min Max
Factory
setting
0 3
0
Summary of Contents for sinamics dcp
Page 2: ......
Page 6: ...Preface SINAMICS DCP 6 List Manual LH21 05 2016 ...
Page 8: ...Table of contents SINAMICS DCP 8 List Manual LH21 05 2016 ...
Page 510: ...A Appendix A 2 List of abbreviations SINAMICS DCP 510 List Manual LH21 05 2016 ...
Page 516: ...Index SINAMICS DCP 516 List Manual LH21 05 2016 ...
Page 517: ...Siemens Parts ...