SINAMICS DCP
List Manual (LH21), 05/2016
275
2 Parameters
2.2 List of parameters
Points along the characteristic:
r54040[0]: current value characteristic point 0
r54041[0]: power value characteristic point 0
r54040[1]: current value characteristic point 1
r54041[1]: power value characteristic point 1
...
r54040[31]: current value characteristic point 31
r54041[31]: power value characteristic point 31
Dependency:
Refer to: r54041
Note:
MPP: maximum power point (point along the characteristic with the maximum power)
Description:
Displays the power values of the last PV array characteristic that was plotted.
Points along the characteristic:
r54040[0]: current value characteristic point 0
r54041[0]: power value characteristic point 0
r54040[1]: current value characteristic point 1
r54041[1]: power value characteristic point 1
...
r54040[31]: current value characteristic point 31
r54041[31]: power value characteristic point 31
Note:
MPP: maximum power point (point along the characteristic with the maximum power)
Description:
Sets the signal source for the voltage controller setpoint.
Description:
Sets the ramp-up time/ramp-down time for the voltage controller setpoint.
The setpoint change is limited so that the setpoint can change by a maximum of 100 % in the time that is set here.
Description:
Selects the signal source for the voltage actual value.
Value:
1:
Actual value voltage side 1
2:
Actual value voltage side 2
3:
Actual value voltage inner side 1
4:
Actual value voltage inner side 2
r54041[0...31]
MPP tracker characteristic power / MPPT char P
DCP_CTRL
Can be changed:
-
Access level:
2
Data type:
FloatingPoint32
Func. diagram:
6700
Min Max
Factory
setting
- [kW]
- [kW]
- [kW]
p54100
CI: Voltage controller setpoint signal source / U_ctrl setp s_src
DCP_CTRL
Can be changed:
T
Access level:
2
Data type:
Unsigned32 / FloatingPoint32
Func. diagram:
6818
Min Max
Factory
setting
- -
1
p54101
Voltage controller ramp-up time/ramp-down time / U_ctrl t_RU/t_RD
DCP_CTRL
Can be changed:
U, T
Access level:
2
Data type:
FloatingPoint32
Func. diagram:
6818
Min Max
Factory
setting
0.000 [s]
10.000 [s]
0.050 [s]
p54102
Voltage controller actual value selection / U_ctrl act val sel
DCP_CTRL
Can be changed:
T
Access level:
2
Data type:
Integer16
Func. diagram:
6818
Min Max
Factory
setting
1 4
3
Summary of Contents for sinamics dcp
Page 2: ......
Page 6: ...Preface SINAMICS DCP 6 List Manual LH21 05 2016 ...
Page 8: ...Table of contents SINAMICS DCP 8 List Manual LH21 05 2016 ...
Page 510: ...A Appendix A 2 List of abbreviations SINAMICS DCP 510 List Manual LH21 05 2016 ...
Page 516: ...Index SINAMICS DCP 516 List Manual LH21 05 2016 ...
Page 517: ...Siemens Parts ...