SINAMICS DCP
List Manual (LH21), 05/2016
137
2 Parameters
2.2 List of parameters
Note:
When changing p4056, the parameters of the scaling characteristic (p4057, p4058, p4059, p4060) are overwritten
with the following default values:
For p4056 = 0, 4, p4057 is set to 0.0 V, p4058 to 0.0 %, p4059 to 10.0 V and p4060 to 100.0 %.
For p4056 = 2, 5, p4057 is set to 0.0 mA, p4058 to 0.0 %, p4059 to 20.0 mA and p4060 to 100.0 %.
For p4056 = 3, p4057 is set to 4.0 mA, p4058 to 0.0 %, p4059 to 20.0 mA and p4060 to 100.0 %.
Description:
Sets the scaling characteristic for the analog inputs of Terminal Module 31 (TM31).
The scaling characteristic for the analog inputs is defined using 2 points.
This parameter specifies the x coordinate (input voltage in V or input current in mA) of the 1st value pair of the
characteristic.
Index:
[0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Dependency:
The unit of this parameter (V or mA) depends on the analog input type.
Refer to: p4056
Notice:
This parameter is automatically overwritten when the analog input type (p4056) is modified.
Note:
The parameters for the characteristic do not have a limiting effect.
Description:
Sets the scaling characteristic for the analog inputs of Terminal Module 31 (TM31).
The scaling characteristic for the analog inputs is defined using 2 points.
This parameter specifies the y coordinate (percentage) of the 1st value pair of the characteristic.
Index:
[0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Notice:
This parameter is automatically overwritten when the analog input type (p4056) is modified.
Note:
The parameters for the characteristic do not have a limiting effect.
Description:
Sets the scaling characteristic for the analog inputs of Terminal Module 31 (TM31).
The scaling characteristic for the analog inputs is defined using 2 points.
This parameter specifies the x coordinate (input voltage in V or input current in mA) of the 2nd value pair of the
characteristic.
Index:
[0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Dependency:
The unit of this parameter (V or mA) depends on the analog input type.
Refer to: p4056
Notice:
This parameter is automatically overwritten when the analog input type (p4056) is modified.
Note:
The parameters for the characteristic do not have a limiting effect.
p4057[0...1]
TM31 analog inputs characteristic value x1 / TM31 AI char x1
TM31
Can be changed:
U, T
Access level:
2
Data type:
FloatingPoint32
Func. diagram:
9566, 9568
Min Max
Factory
setting
-20.000 20.000
0.000
p4058[0...1]
TM31 analog inputs characteristic value y1 / TM31 AI char y1
TM31
Can be changed:
U, T
Access level:
2
Data type:
FloatingPoint32
Func. diagram:
9566, 9568
Min Max
Factory
setting
-1000.00 [%]
1000.00 [%]
0.00 [%]
p4059[0...1]
TM31 analog inputs characteristic value x2 / TM31 AI char x2
TM31
Can be changed:
U, T
Access level:
2
Data type:
FloatingPoint32
Func. diagram:
9566, 9568
Min Max
Factory
setting
-20.000 20.000
10.000
Summary of Contents for sinamics dcp
Page 2: ......
Page 6: ...Preface SINAMICS DCP 6 List Manual LH21 05 2016 ...
Page 8: ...Table of contents SINAMICS DCP 8 List Manual LH21 05 2016 ...
Page 510: ...A Appendix A 2 List of abbreviations SINAMICS DCP 510 List Manual LH21 05 2016 ...
Page 516: ...Index SINAMICS DCP 516 List Manual LH21 05 2016 ...
Page 517: ...Siemens Parts ...