2 Parameters
2.2 List of parameters
SINAMICS DCP
282
List Manual (LH21), 05/2016
Value:
0:
Deactivated
1:
Activated
Dependency:
Refer to: p54990, p54991, p54992, r54994
Description:
Display and connector output for the values in the EEPROM on the mainboard.
Dependency:
Refer to: p54990, p54991, p54992, p54993
Description:
Sets the signal source for the current setpoint.
Description:
Sets the ramp-up time/ramp-down time for the current setpoint.
The current setpoint change is limited so that the setpoint can change by a maximum of 100 % in the time that is set
here.
Description:
Sets the absolute value of the minimum current setpoint.
Description:
Sets the significance for the setpoint.
Value:
10:
Reactor current
11:
Current side 1
12:
Current side 2
20:
Power
Note:
The current actual value sensing in SINAMICS DCP measures the reactor current.
The specified setpoint is converted into a reactor current setpoint and this is used for the closed-loop current control.
For value = 10:
Reactor current setpoint = setpoint (no conversion)
For value = 11:
The current at side 1 is specified as setpoint.
If U1 <= U2: reactor current setpoint = setpoint (no conversion)
If U1 > U2: reactor current setpoint = setpoint * U1/U2
r54994[0...31]
CO: Mainboard diagnostics EEPROM display values / EEPROM disp_values
DCP_CTRL
Can be changed:
-
Access level:
4
Data type:
Unsigned8
Func. diagram:
8055
Min Max
Factory
setting
- -
-
p55050
CI: Voltage controller setpoint signal source / I_set s_src
DCP_CTRL
Can be changed:
U, T
Access level:
2
Data type:
Unsigned32 / FloatingPoint32
Func. diagram:
6805
Min Max
Factory
setting
- -
2050[1]
p55055
Current setpoint ramp-up time/ramp-down time / I_set t_RU/t_RD
DCP_CTRL
Can be changed:
U, T
Access level:
2
Data type:
FloatingPoint32
Func. diagram:
6805
Min Max
Factory
setting
0.000 [s]
10.000 [s]
0.050 [s]
p55056
Current setpoint minimum threshold / I_set min thresh
DCP_CTRL
Can be changed:
U, T
Access level:
2
Data type:
FloatingPoint32
Func. diagram:
6805
Min Max
Factory
setting
0.00 [%]
50.00 [%]
0.40 [%]
p55060
Current setpoint significance / I_set significance
DCP_CTRL
Can be changed:
U, T
Access level:
1
Data type:
Integer16
Func. diagram:
6806
Min Max
Factory
setting
10 20
11
Summary of Contents for sinamics dcp
Page 2: ......
Page 6: ...Preface SINAMICS DCP 6 List Manual LH21 05 2016 ...
Page 8: ...Table of contents SINAMICS DCP 8 List Manual LH21 05 2016 ...
Page 510: ...A Appendix A 2 List of abbreviations SINAMICS DCP 510 List Manual LH21 05 2016 ...
Page 516: ...Index SINAMICS DCP 516 List Manual LH21 05 2016 ...
Page 517: ...Siemens Parts ...