4 Faults and alarms
4.2 List of faults and alarms
SINAMICS DCP
444
List Manual (LH21), 05/2016
A07851 (F)
External alarm 2
Drive object:
All objects
Cause:
The condition for "External alarm 2" is satisfied.
Note:
The "External alarm 2" is initiated by a 1/0 edge via binector input p2116.
See also: p2116 (External alarm 2)
Remedy:
Eliminate the causes of this alarm.
A07852 (F)
External alarm 3
Drive object:
All objects
Cause:
The condition for "External alarm 3" is satisfied.
Note:
The "External alarm 3" is initiated by a 1/0 edge via binector input p2117.
See also: p2117 (External alarm 3)
Remedy:
Eliminate the causes of this alarm.
F07860 (A)
External fault 1
Drive object:
All objects
Cause:
The condition for "External fault 1" is satisfied.
Note:
The "External fault 1" is initiated by a 1/0 edge via binector input p2106.
See also: p2106 (External fault 1)
Remedy:
- eliminate the causes of this fault.
- acknowledge fault.
F07861 (A)
External fault 2
Drive object:
All objects
Cause:
The condition for "External fault 2" is satisfied.
Note:
The "External fault 2" is initiated by a 1/0 edge via binector input p2107.
See also: p2107 (External fault 2)
Remedy:
- eliminate the causes of this fault.
- acknowledge fault.
F07862 (A)
External fault 3
Drive object:
All objects
Cause:
The condition for "External fault 3" is satisfied.
Note:
The "External fault 3" is initiated by a 1/0 edge via the following parameters.
- AND logic operation, binector input p2108, p3111, p3112.
- switch-on delay p3110.
See also: p2108, p3110, p3111, p3112
Remedy:
- eliminate the causes of this fault.
- acknowledge fault.
F08000 (N, A)
TB: +/-15 V power supply faulted
Drive object:
TM150, TM15DI_DO, TM31
Cause:
Terminal Board 30 detects an incorrect internal power supply voltage.
Fault value (r0949, interpret decimal):
0: Error when testing the monitoring circuit.
1: Fault in normal operation.
Remedy:
- replace Terminal Board 30.
- replace Control Unit.
Summary of Contents for sinamics dcp
Page 2: ......
Page 6: ...Preface SINAMICS DCP 6 List Manual LH21 05 2016 ...
Page 8: ...Table of contents SINAMICS DCP 8 List Manual LH21 05 2016 ...
Page 510: ...A Appendix A 2 List of abbreviations SINAMICS DCP 510 List Manual LH21 05 2016 ...
Page 516: ...Index SINAMICS DCP 516 List Manual LH21 05 2016 ...
Page 517: ...Siemens Parts ...