2 Parameters
2.2 List of parameters
SINAMICS DCP
46
List Manual (LH21), 05/2016
Description:
Sets the signal source to select the Command Data Set bit 0 (CDS bit 0).
Dependency:
Refer to: r0050, r0836
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
The Command Data Set selected using the binector inputs is displayed in r0836.
The currently effective command data set is displayed in r0050.
A Command Data Set can be copied using p0809.
Description:
Copies one Drive Data Set (DDS) into another.
Index:
[0] = Source Drive Data Set
[1] = Target Drive Data Set
[2] = Start copying procedure
Note:
Procedure:
1. In Index 0, enter which drive data set is to be copied.
2. In Index 1, enter the drive data set data that is to be copied into.
3. Start copying: Set index 2 from 0 to 1.
p0819[2] is automatically set to 0 when copying is completed.
Description:
Sets the signal source to select the Drive Data Set, bit 0 (DDS, bit 0).
Dependency:
Refer to: r0051, r0837
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description:
Sets the signal source to select the Drive Data Set, bit 1 (DDS, bit 1).
Dependency:
Refer to: r0051, r0837
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description:
Displays the status word for the drive data set changeover.
p0810
BI: Command data set selection CDS bit 0 / CDS select., bit 0
DCP_CTRL
Can be changed:
T
Access level:
3
Data type:
Unsigned32 / Binary
Func. diagram:
8560
Min Max
Factory
setting
- -
0
p0819[0...2]
Copy Drive Data Set DDS / Copy DDS
DCP_CTRL
Can be changed:
C2(15)
Access level:
2
Data type:
Unsigned8
Func. diagram:
8565
Min Max
Factory
setting
0 31
0
p0820[0...n]
BI: Drive Data Set selection DDS bit 0 / DDS select., bit 0
DCP_CTRL
Can be changed:
C2(15), T
Access level:
3
Data type:
Unsigned32 / Binary
Func. diagram:
8565, 8570
Min Max
Factory
setting
- -
0
p0821[0...n]
BI: Drive Data Set selection DDS bit 1 / DDS select., bit 1
DCP_CTRL
Can be changed:
C2(15), T
Access level:
3
Data type:
Unsigned32 / Binary
Func. diagram:
8565, 8570
Min Max
Factory
setting
- -
0
r0835.2
CO/BO: Data set changeover status word / DDS_ZSW
DCP_CTRL
Can be changed:
-
Access level:
2
Data type:
Unsigned16
Func. diagram:
8575
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
02
Internal parameter calculation active
Yes
No
-
Summary of Contents for sinamics dcp
Page 2: ......
Page 6: ...Preface SINAMICS DCP 6 List Manual LH21 05 2016 ...
Page 8: ...Table of contents SINAMICS DCP 8 List Manual LH21 05 2016 ...
Page 510: ...A Appendix A 2 List of abbreviations SINAMICS DCP 510 List Manual LH21 05 2016 ...
Page 516: ...Index SINAMICS DCP 516 List Manual LH21 05 2016 ...
Page 517: ...Siemens Parts ...