4 Faults and alarms
4.2 List of faults and alarms
A40101
Alarm at DRIVE-CLiQ socket X101
Drive object:
CU_DCP, TM150, TM15DI_DO, TM31
Cause:
An alarm has occurred at the drive object at the DRIVE-CLiQ socket X101.
Alarm value (r2124, interpret decimal):
First alarm that has occurred for this drive object.
Remedy:
Evaluate the alarm buffer of the specified object.
A40102
Alarm at DRIVE-CLiQ socket X102
Drive object:
TM150, TM15DI_DO, TM31
Cause:
An alarm has occurred at the drive object at the DRIVE-CLiQ socket X102.
Alarm value (r2124, interpret decimal):
First alarm that has occurred for this drive object.
Remedy:
Evaluate the alarm buffer of the specified object.
A40103
Alarm at DRIVE-CLiQ socket X103
Drive object:
TM150, TM15DI_DO, TM31
Cause:
An alarm has occurred at the drive object at the DRIVE-CLiQ socket X103.
Alarm value (r2124, interpret decimal):
First alarm that has occurred for this drive object.
Remedy:
Evaluate the alarm buffer of the specified object.
A40104
Alarm at DRIVE-CLiQ socket X104
Drive object:
TM150, TM15DI_DO, TM31
Cause:
An alarm has occurred at the drive object at the DRIVE-CLiQ socket X104.
Alarm value (r2124, interpret decimal):
First alarm that has occurred for this drive object.
Remedy:
Evaluate the alarm buffer of the specified object.
A40105
Alarm at DRIVE-CLiQ socket X105
Drive object:
TM150, TM15DI_DO, TM31
Cause:
An alarm has occurred at the drive object at the DRIVE-CLiQ socket X105.
Alarm value (r2124, interpret decimal):
First alarm that has occurred for this drive object.
Remedy:
Evaluate the alarm buffer of the specified object.
F40799
CX32: Configured transfer end time exceeded
Drive object:
TM150, TM15DI_DO, TM31
Cause:
The configured transfer end time when transferring the cyclic actual values was exceeded.
Remedy:
- carry out a POWER ON (power off/on) for all components.
- contact the Hotline.
F40801
CX32 DRIVE-CLiQ: Sign-of-life missing
Drive object:
TM150, TM15DI_DO, TM31
Cause:
A DRIVE-CLiQ communications error has occurred from the Control Unit to the controller extension involved.
Fault cause:
10 (= 0A hex):
The sign-of-life bit in the receive telegram is not set.
Note regarding the message value:
The individual information is coded as follows in the message value (r0949/r2124):
0000yyxx hex: yy = component number, xx = error cause
Remedy:
- carry out a POWER ON (power off/on).
- replace the component involved.
Summary of Contents for sinamics dcp
Page 2: ......
Page 6: ...Preface SINAMICS DCP 6 List Manual LH21 05 2016 ...
Page 8: ...Table of contents SINAMICS DCP 8 List Manual LH21 05 2016 ...
Page 510: ...A Appendix A 2 List of abbreviations SINAMICS DCP 510 List Manual LH21 05 2016 ...
Page 516: ...Index SINAMICS DCP 516 List Manual LH21 05 2016 ...
Page 517: ...Siemens Parts ...