Publication 2094-UM001A-EN-P — September 2006
124
Configure and Startup the Kinetix 6000 Drive System
Node Addressing Example 3
In Example 2, the Kinetix 6000 (8-axis) power rail contains a
double-wide IAM, two double-wide AMs, one single-wide AM, and
one slot filler module. The slot filler module is assigned a node
address, but does not use it.
The leftmost slot of a double-wide module determines the node
address. So, in the example above, node addresses 02, 04, and 06 (the
rightmost slots of the double-wide modules) are not used.
SERCOS interface
TM
Tx (rear)
Rx (front)
OK
CP
08 = Slot Filler Node Address
07 = AM (axis 4) Node Address
06 = Not Used (AM Rightmost Slot)
05 = AM (axis 3) Node Address
04 = Not Used (AM Rightmost Slot)
03 = AM (axis 2) Node Address
02 = Not Used (IAM Rightmost Slot)
01 = IAM (axis 1) Base Node Address
Logix Platform
(ControlLogix is shown)
SERCOS Fiber-optic Ring
1756-M
xx
SE SERCOS
interface Module
Kinetix 6000
(8-axis power rail)
Receive
Transmit
Transmit
Receive
IMPORTANT
Slot filler modules must be used to fill any unoccupied slot on
the power rail. However, the slot fillers may also be removed
and replaced by an axis or shunt module in the future.
IMPORTANT
Do not position axis modules to the right of shunt or slot filler
modules. The added distance between non-adjacent axes can
increase electrical noise and impedance, and requires longer
fiber-optic cable lengths.
Summary of Contents for Allen-Bradley Kinetix 6000
Page 8: ...Publication 2094 UM001A EN P September 2006 8 Table of Contents...
Page 18: ...Publication 2094 UM001A EN P September 2006 18 Start...
Page 118: ...Publication 2094 UM001A EN P September 2006 118 Connecting the Kinetix 6000 Drive System...
Page 190: ...Publication 2094 UM001A EN P September 2006 190 Specifications and Dimensions...
Page 265: ...Publication 2094 UM001A EN P September 2006 265 Notes...
Page 266: ...Publication 2094 UM001A EN P September 2006 266 Notes...
Page 267: ...Publication 2094 UM001A EN P September 2006 267 Notes...