Publication 2094-UM001A-EN-P — September 2006
Kinetix 6000 Connector Data
65
Control Power Input
The integrated axis module (IAM) requires ac input power for logic
circuitry.
Control Power Current Specifications
Control Power Current Requirements
IMPORTANT
The control power input requires an ac (EMC) line filter for CE
certification. For wiring examples, refer to Power Wiring
Examples beginning on page 193.
IMPORTANT
Source 2094-AC
xx
-M
xx
(230V)
IAM control power from the
three-phase input power (line-to-line). Supplying 230V control
power from any other source requires an isolation transformer.
If used, do not ground either leg of the isolation transformer
output. Control power isolation, via a step-down transformer, is
required for all 460V applications.
Refer to Transformer Specifications for Control Power Input on
page 179.
Specification
Description
Input voltage
95...264V ac rms, single-phase
Input power frequency
47...63 Hz
Number of Axis
Modules
(1)
(1)
This number does not include the axis module (inverter section) that resides inside the integrated axis module.
Current Requirements
(110/115V ac input)
Current Requirements
(220/230V ac input)
Input VA
0
750 mA
350 mA
150 VA
1
1.5 A
700 mA
200 VA
2
2.25 A
1 A
275 VA
3
3 A
1.35 A
350 VA
4
3.75 A
1.7 A
450 VA
5
4.5 A
2 A
550 VA
6
5.25 A
2.4 A
650 VA
7
6 A
3 A
750 VA
Summary of Contents for Allen-Bradley Kinetix 6000
Page 8: ...Publication 2094 UM001A EN P September 2006 8 Table of Contents...
Page 18: ...Publication 2094 UM001A EN P September 2006 18 Start...
Page 118: ...Publication 2094 UM001A EN P September 2006 118 Connecting the Kinetix 6000 Drive System...
Page 190: ...Publication 2094 UM001A EN P September 2006 190 Specifications and Dimensions...
Page 265: ...Publication 2094 UM001A EN P September 2006 265 Notes...
Page 266: ...Publication 2094 UM001A EN P September 2006 266 Notes...
Page 267: ...Publication 2094 UM001A EN P September 2006 267 Notes...