Publication 2094-UM001A-EN-P — September 2006
100
Connecting the Kinetix 6000 Drive System
Pigtail Terminations
TL- and Y-Series motors have a short pigtail cable which connects to
the motor, but is not shielded. The preferred method for grounding
the TL- and Y-Series motor power cable on the motor side is to
expose a section of the cable shield and clamp it directly to the
machine frame. The motor power cable also has a 150 mm (6.0 in.)
shield termination wire with a ring lug that connects to the closest
earth ground. Use this method in addition to the cable clamp. The
termination wire may be extended to the full length of the motor
pigtail if necessary, but it is best to connect the supplied wire directly
to ground without lengthening.
Pigtail Terminations
(1)
Remove paint from machine frame to ensure proper HF-bond between machine frame and motor case, shield
clamp, and ground stud.
(1)
(1)
Pigtail Cable
TL-Series or
Y-Series
Motor
Connectors
Motor Power Cable
Machine Frame
150 mm (6.0) Termination
Cable Braid Clamped
to Machine Frame.
(1)
Summary of Contents for Allen-Bradley Kinetix 6000
Page 8: ...Publication 2094 UM001A EN P September 2006 8 Table of Contents...
Page 18: ...Publication 2094 UM001A EN P September 2006 18 Start...
Page 118: ...Publication 2094 UM001A EN P September 2006 118 Connecting the Kinetix 6000 Drive System...
Page 190: ...Publication 2094 UM001A EN P September 2006 190 Specifications and Dimensions...
Page 265: ...Publication 2094 UM001A EN P September 2006 265 Notes...
Page 266: ...Publication 2094 UM001A EN P September 2006 266 Notes...
Page 267: ...Publication 2094 UM001A EN P September 2006 267 Notes...