Publication 2094-UM001A-EN-P — September 2006
Planning the Kinetix 6000 Drive System Installation
21
Transformer Selection
The integrated axis module (IAM) does not require an isolation
transformer for three-phase input power. However, a transformer may
be required to match the voltage requirements of the controller to the
available service.
To size a transformer for the main ac power inputs, refer to the Circuit
Breaker/Fuse Specifications on page 177 and Transformer
Specifications for Control Power Input on page 179.
Example: Sizing a transformer to the voltage requirements of a
2094-AC05-M01 Integrated Axis Module:
2094-AC05-M01 = 3 kW continuous x 1.5 = 4.5 KVA transformer
IMPORTANT
If using an autotransformer, make sure that the phase to
neutral/ground voltages do not exceed the input voltage ratings
of the drive.
IMPORTANT
Use a form factor of 1.5 for three-phase power (where form
factor is used to compensate for transformer, drive module and
motor losses, and to account for utilization in the intermittent
operating area of the torque speed curve).
Summary of Contents for Allen-Bradley Kinetix 6000
Page 8: ...Publication 2094 UM001A EN P September 2006 8 Table of Contents...
Page 18: ...Publication 2094 UM001A EN P September 2006 18 Start...
Page 118: ...Publication 2094 UM001A EN P September 2006 118 Connecting the Kinetix 6000 Drive System...
Page 190: ...Publication 2094 UM001A EN P September 2006 190 Specifications and Dimensions...
Page 265: ...Publication 2094 UM001A EN P September 2006 265 Notes...
Page 266: ...Publication 2094 UM001A EN P September 2006 266 Notes...
Page 267: ...Publication 2094 UM001A EN P September 2006 267 Notes...