Publication 2094-UM001A-EN-P — September 2006
Connecting the Kinetix 6000 Drive System
79
For power rail dimensions, refer to the Kinetix 6000 Power Rail
Installation Instructions, publication 2094-IN003.
For mounting bracket dimensions, refer to the 2094 Mounting
Brackets Installation Instructions, publication 2094-IN008.
Grounding Multiple Subpanels
Extending the chassis ground to multiple subpanels is illustrated in the
figure below. High-frequency (HF) bonding is not illustrated.
Subpanels Connected to a Single Ground Point
For HF bonding information, refer to Bonding Multiple Subpanels on
page 29.
IMPORTANT
When 2094 mounting brackets are used to mount the power rail
or LIM over the ac line filter, the braided ground strap must be
removed from the power rail and attached to a mounting
bracket ground stud.
Follow NEC and
applicable local codes.
Bonded Ground Bus
Ground Grid or Power
Distribution Ground