Publication 2094-UM001A-EN-P — September 2006
Troubleshooting the Kinetix 6000 Drive System
151
E79
DriveOvervoltage
Fault
(Shunt Module Flt)
Shunt module temperature fault LED indicator is steady red.
Refer to Temperature Fault LED Indicator
on page 154.
Shunt module shunt fault LED indicator is steady red.
Refer to Shunt Fault LED Indicator on page
154.
Module missing from power rail.
• Install missing module on power rail.
• Fill empty slot with slot filler module.
E80
DriveHardFault
(CPLD Flt)
Control hardware fault detected.
Replace module.
E81
DriveHardFault
(Common Bus Flt)
Follower IAM detected ac input power being applied.
Remove ac input power connections from
follower IAM.
E90
DriveHardFault
(Pre-charge Timeout Flt)
Pre-charge resistor power exceeds the resistor rating.
Allow resistor to cool.
All
others
RESERVED
Call your local Rockwell Automation sales
representative.
Error
Code
Fault Message
RSLogix
(HIM)
Problem or Symptom
Potential Cause
Possible Resolution
Summary of Contents for Allen-Bradley Kinetix 6000
Page 8: ...Publication 2094 UM001A EN P September 2006 8 Table of Contents...
Page 18: ...Publication 2094 UM001A EN P September 2006 18 Start...
Page 118: ...Publication 2094 UM001A EN P September 2006 118 Connecting the Kinetix 6000 Drive System...
Page 190: ...Publication 2094 UM001A EN P September 2006 190 Specifications and Dimensions...
Page 265: ...Publication 2094 UM001A EN P September 2006 265 Notes...
Page 266: ...Publication 2094 UM001A EN P September 2006 266 Notes...
Page 267: ...Publication 2094 UM001A EN P September 2006 267 Notes...