Publication 2094-UM001A-EN-P — September 2006
Troubleshooting the Kinetix 6000 Drive System
159
No Fault Message
(condition indicated by
on-screen message)
(Atune Flt)
E66
Autotune procedure failed.
DISABLE
N
DriveHardFault
(Task init)
E67
Operating system failed.
SHUTDOWN
N
DriveHardFault
(SCANport Comm)
E68
DPI communication failed.
STOP
N
DriveHardFault
(Objects Init)
E69
Non-volatile memory attribute out of range.
SHUTDOWN
N
DriveHardFault
(NV Mem Init)
E70
Non-volatile memory corrupted.
SHUTDOWN
N
DriveHardFault
(Memory Init)
E71
RAM or flash memory validation failure.
SHUTDOWN
N
DriveOvertempFault
(Drive Overtemp)
E72
Inverter temperature limit exceeded.
Firmware I
2
t protection does not generate a fault, rather it
dynamically folds back current when 110% of drive rating is reached.
SHUTDOWN
Y
Communicate
(Backplane Comm)
E73
Power rail backplane CAN communications failed.
STOP
N
DriveOvercurrentFault
(Bus OverCurrent)
E74
The converter has exceeded its converter rating.
SHUTDOWN
N
DriveOvervoltageFault
(Shunt Time Out)
E75
The IAM, AM, or SM has exceeded its shunt resistor continuous
rating. SHUTDOWN for IAM, DISABLE for AM. IAM also provides
fault handling for shunt module.
SHUTDOWN
N
DriveHardFault
(Can Init)
E76
Either DPI or backplane CAN initialization failure.
SHUTDOWN
N
DriveHardFault
(Module Mismatch)
E77
Generated by IAM if the power rating of an AM on the same power
rail does not match with IAM input power rating.
SHUTDOWN
N
DriveHardFault
SERCOS Init
E78
Control hardware fault detected.
SHUTDOWN
N
DriveOvervoltageFault
(Shunt Module Flt)
E79
Power rail mounted shunt module fault. Displayed on IAM
seven-segment fault status LED indicator.
SHUTDOWN
N
HardwareFault
(CPLD Flt)
E80
Control hardware fault detected.
SHUTDOWN
N
HardwareFault
(Common Bus Flt)
E81
Common bus follower IAM detected ac input power being applied.
SHUTDOWN
N
HardwareFault
(Pre-charge Timeout Flt)
E90
Pre-charge resistor power exceeds the resistor rating.
SHUTDOWN
N
RESERVED
All
Others
Fault Message RSLogix
(HIM)
Error
Code
Description
Drive Fault
Action
RSLogix
Programmable
Fault Action?
Summary of Contents for Allen-Bradley Kinetix 6000
Page 8: ...Publication 2094 UM001A EN P September 2006 8 Table of Contents...
Page 18: ...Publication 2094 UM001A EN P September 2006 18 Start...
Page 118: ...Publication 2094 UM001A EN P September 2006 118 Connecting the Kinetix 6000 Drive System...
Page 190: ...Publication 2094 UM001A EN P September 2006 190 Specifications and Dimensions...
Page 265: ...Publication 2094 UM001A EN P September 2006 265 Notes...
Page 266: ...Publication 2094 UM001A EN P September 2006 266 Notes...
Page 267: ...Publication 2094 UM001A EN P September 2006 267 Notes...