Publication 2094-UM001A-EN-P — September 2006
80
Connecting the Kinetix 6000 Drive System
Power Wiring
Requirements
Wire should be copper with 75
°
C (167
°
F) minimum rating. Phasing
of main ac power is arbitrary and earth ground connection is required
for safe and proper operation.
IAM Power Wiring Requirements
IMPORTANT
The National Electrical Code and local electrical codes take
precedence over the values and methods provided.
Module
Catalog Number
Description
Connects to Terminals
Recommended
Wire Size
mm
2
(AWG)
Strip Length
mm (in.)
Torque Value
Nm (lb-in)
Pin
Signal
IAM
(230V)
2094-AC05-M
xx
-S
2094-AC09-M
xx
-S
DC bus
(1)
and
VAC input power
IPD-1
IPD-2
IPD-3
IPD-4
IPD-5
IPD-6
2.5 (14)
10 (0.38)
0.5 - 0.6
(4.4 - 5.3)
2094-AC16-M
xx
-S
10 (8)
16 (0.63)
2.4 - 3.0
(21.6 - 26.5)
2094-AC32-M
xx
-S
25 (4)
IAM
(460V)
2094-BC01-M
xx
-S
2094-BC02-M
xx
-S
4.0 (12)
10 (0.38)
1.2 - 1.5
(10.6 - 13.2)
2094-BC04-M
xx
-S
10 (8)
16 (0.63)
2.4 - 3.0
(21.6 - 26.5)
2094-BC07-M
xx
-S
25 (4)
IAM
(230V or 460V)
2094-
x
C
xx
-M
xx
-S
Control input power
CPD-1
CTRL 2
2.5 (14)
10 (0.38)
0.5 - 0.6
(4.4 - 5.3)
CPD-2
CTRL 1
Contactor Enable
CED-1
CONT EN-
2.5 (14)
(2)
0.5 - 0.6
(4.4 - 5.3)
CED-2
CONT EN+
(1)
DC common bus connections (leader IAM to follower IAM) should be kept as short as possible.
(2)
The actual gauge of the contactor enable wiring depends on the system configuration. Consult your machine builder, the NEC, and applicable local codes.
L3
L2
L1
DC-
DC+
ATTENTION
To avoid personal injury and/or equipment damage, make sure
installation complies with specifications regarding wire types,
conductor sizes, branch circuit protection, and disconnect
devices. The National Electrical Code (NEC) and local codes
outline provisions for safely installing electrical equipment.
To avoid personal injury and/or equipment damage, make sure
motor power connectors are used for connection purposes only.
Do not use them to turn the unit on and off.
To avoid personal injury and/or equipment damage, make sure
shielded power cables are grounded to prevent potentially high
voltages on the shield.
Summary of Contents for Allen-Bradley Kinetix 6000
Page 8: ...Publication 2094 UM001A EN P September 2006 8 Table of Contents...
Page 18: ...Publication 2094 UM001A EN P September 2006 18 Start...
Page 118: ...Publication 2094 UM001A EN P September 2006 118 Connecting the Kinetix 6000 Drive System...
Page 190: ...Publication 2094 UM001A EN P September 2006 190 Specifications and Dimensions...
Page 265: ...Publication 2094 UM001A EN P September 2006 265 Notes...
Page 266: ...Publication 2094 UM001A EN P September 2006 266 Notes...
Page 267: ...Publication 2094 UM001A EN P September 2006 267 Notes...