8 CIP Message Communications
8-44
NY-series Industrial Panel PC / Industrial Box PC Built-in EtherNet/IP Port User’s Manual (W563)
This object is used to read and write settings such as the IP address, subnet mask, and default gate-
way.
Specify the service to execute with the service code.
Specify F5 hex.
Specify 00 to 02 hex.
00: Specify the class
01: Built-in EtherNet/IP port
02: Internal port
The attribute ID specifies the information to read.
Class Attribute ID
The class attribute ID specifies the attribute of the entire object.
8-5-3
TCP/IP Interface Object (Class ID: F5 hex)
Service Codes
Service
code
Parameter name
Description
Supported services
Classes
Instances
01 hex
Get_Attribute_All
Reads the values of the attributes.
Sup-
ported.
Not sup-
ported.
0E hex
Get_Attribute_Single
Reads the value of the specified attribute.
Sup-
ported.
Sup-
ported.
10 hex
Set_Attribute_Single
Writes a value to the specified attribute. The built-in EtherNet/IP port
restarts automatically after the value is written to the attribute. When
the restart process is not completed and the next Set_Attribute_Single
is executed, the general status “0C hex” (Object State Conflict) is
returned.
Not sup-
ported.
Sup-
ported.
Class ID
Instance ID
Attribute ID
Attribute ID
Parameter name
Description
Attribute
Read data
Data
type
Value
01 hex
Revision
Revision of the object
Read
UINT
0004 hex
02 hex
Max Instance
The maximum instance number
Read
UINT
0002 hex
03 hex
Num of Instance
The number of object instance
Read
UINT
0002 hex
Summary of Contents for Sysmac NY512-1300