8-27
8 CIP Message Communications
NY-series Industrial Panel PC / Industrial Box PC Built-in EtherNet/IP Port User’s Manual (W563)
8-2
CIP Messag
ing C
o
m
m
u
n
icat
ions
Client
Fu
nct
ion
8
8-2
-9 Operation T
iming
You can monitor the values of the output variables to determine the status throughout instruction exe-
cution. The following timing chart shows the operation of the output variables.
1
When
Execute
changes to TRUE, the instruction is executed and
Busy
changes to TRUE.
2
After the results of instruction execution are stored in the output variables,
Done
changes to
TRUE and
Busy
changes to FALSE.
3
When
Execute
changes to FALSE,
Done
returns to FALSE.
4
When
Execute
changes to TRUE again,
Busy
changes to TRUE.
5
Execute
is ignored if it changes to TRUE during instruction executed (i.e., when
Busy
is TRUE).
6
If an error occurs, several retries are attempted internally. The error code in the
ErrorID
is not
updated during the retries.
7
When a communications error occurs,
Error
changes to TRUE and the
ErrorID
is stored. Also,
Busy
and
Done
change to FALSE.
8
When
Execute
changes to FALSE,
Error
changes to FALSE.
8-2-9
Operation Timing
Output Variable Operation and Timing
(7)
Execute
0x1234
0x0000
ErrorID
Error
Done
Busy
(Executing)
(1)
(2)
(3)
(4)
(5)
(6)
(8)
Changes to FALSE
because
Execute
changes to FALSE.
Changes to FALSE
because
Execute
changes to FALSE.