![background image](http://html.mh-extra.com/html/omron/sysmac-ny512-1300/sysmac-ny512-1300_user-manual_742451034.webp)
1 Introduction
1-8
NY-series Industrial Panel PC / Industrial Box PC Built-in EtherNet/IP Port User’s Manual (W563)
*1 If tag data links are being used, use 100Base-TX or 1000Base-T.
*2 Here, pps means “packets per second” and indicates the number of packets that can be processed in one sec-
ond.
*3 To use a data size of 505 bytes or higher, the system must support a large forward open (an optional CIP spec-
ification). The CS, CJ, NJ, NX, and NY-series Units support a large forward open, but before connecting to
nodes of other companies, confirm that those devices also support it.
*4 If the parameters of the built-in EtherNet/IP port are changed, the port is restarted. When other nodes are in
communications with the affected node, the communications will temporarily time out and automatically
recover after the restart.
*5 Because the built-in EtherNet/IP port is equipped with an IGMP client (version 2), unnecessary multicast pack-
ets can be filtered by an Ethernet switch that supports IGMP snooping.
CIP service: Tag
data links (cyclic
communications)
Number of tags per
connection (= 1 tag
set)
8 (7 tags when the tag set contains the Controller status)
Maximum link data
size per node
184,832 bytes
Maximum data size
per connection
1,444 bytes
*3
Data concurrency is maintained within each connection. Refer to
7-1-7 Concurrency of Tag Data Link Data
concurrency.
Number of regis-
trable tag sets
128 (1 connection = 1 tag set)
Maximum size of 1
tag set
722 words (The Controller status uses 1 word when the tag set
contains the Controller status.)
Changing tag data
link parameters
when Controller is
in RUN mode
Supported
*4
Multi-cast packet
filter
*5
Supported
CIP message ser-
vice: Explicit mes-
sages
*6
Class 3 (con-
nected)
Number of connections: 64 (c servers)
UCMM (uncon-
nected)
Number of clients that can communicate at one time: 32 max.
Number of servers that can communicate at one time: 32 max.
CIP routing
Supported.
CIP routing is supported for the following remote Units: NY5
2-
, NX701-
, NJ501-
, NJ301-
,
NJ101-
, CS1W-EIP21, CJ1W-EIP21, CJ2H-CPU
-EIP,
and CJ2M-CPU3
.
Using a combination of any Units above, communication can be
extended up to a maximum of 8 levels.
SNMP
Agents
SNMPv1 or SNMPv2c
MIB
MIB-II
EtherNet/IP conformance test
Conforms to CT13
Ethernet interface
10Base-T, 100Base-TX, or 1000Base-T
Auto negotiation or fixed settings
Item
Specifications
NY5
2-
Unit version 1.12 or later
Summary of Contents for Sysmac NY512-1300