Appendices
A-62
NY-series Industrial Panel PC / Industrial Box PC Built-in EtherNet/IP Port User’s Manual (W563)
Method 2: Changing the Memory Configuration of the Structure Variable in
the Remote Device
You can insert a member into the structure variable of the remote device to change it to match the
memory configuration of the structure variable in the NY-series Controller. Both the memory configu-
ration and the data types must be the same between the two structure variables. You therefore need
to create the same members in both the remote device and the NY-series Controller.
Example: The following example shows how the memory configuration of the structure variable in
the CJ-series CPU Unit is changed to match the memory configuration of the structure variable in
the NY-series Controller.
a
b
b2
c
a
b
b2
c
a
b
c
Data Type Definitions
Name
Structure
Y
a
b
b2
c
Data type
STRUCT
DINT
INT
INT
DINT
Bytes
CJ-series Structure Variable
CJ_X
First byte
First byte + 4
First byte + 6
First byte + 8
Variable Table
Name
Variable
CJ_X
Data type
Structure
Y
Data Type Definitions
Name
Structure
Y
a
b
b2
c
Data type
STRUCT
DINT
INT
INT
DINT
Bytes
NY-series Structure Variable
NY_X
First byte
First byte + 4
First byte + 6
First byte + 8
Variable Table
Name
Variable
NY_X
Data type
Structure
Y
Data Type Definitions
Name
Structure
Y
a
b
c
Data type
STRUCT
DINT
INT
DINT
Bytes
CJ-series Structure Variable
CJ_X
First byte
First byte + 4
First byte + 6
Variable Table
Name
Variable
CJ_X
Data type
Structure
Y
Data Type Definitions
Name
Structure
Y
a
b
c
Data type
STRUCT
DINT
INT
DINT
Bytes
a
b
Not used.
c
NY-series Structure Variable
NY_X
First byte
First byte + 4
First byte + 6
First byte + 8
Variable Table
Name
Variable
NY_X
Data type
Structure
Y
(2) Add the dummy variable
b2
that you created in the
CJ-series CPU Unit to the NY-series Controller as well.
(1) Add a dummy member variable
b2
that matches the
unused memory location on the NY-series Controller.
Make the following changes to align the memory configurations
in the NY-series Controller and CJ-series CPU Units.