7-35
7 Tag Data Link Functions
NY-series Industrial Panel PC / Industrial Box PC Built-in EtherNet/IP Port User’s Manual (W563)
7-
2 S
e
tti
ng
T
ag
Da
ta
Li
n
ks
7
7-2
-5 Con
nection Settings
The settings are as follows:
2
After you make all of the settings, click the
OK
Button.
Editing Settings for All Connections
You can edit the connection settings between the originator and all of the target devices selected in
the Register Device List together in a table.
1
Click the
Connections
Tab, and then click the
Edit All
Button. The following Edit All Connec-
tions Dialog Box is displayed.
Setting
Description
Connection I/O Type
Select Input Only (tag type) to use tag data links with a CS1W-EIP21, CJ1W-EIP21,
CJ2B-EIP21, CJ2M-EIP21, CJ1W-EIP21(CJ2), CJ1W-EIP21(NJ), NX701, NJ501-
, NJ301-
, NJ101, or NY5
2. When you create tag data links for other
devices, select the connection I/O type specified in that device’s EDS file. Use the Input
Only (ID type) setting when another company’s node is the originator and does not sup-
port connection settings with a Tag type setting.
Connection Type
Select whether the data is sent in multi-cast or unicast (point-to-point) format. The
default setting is multi-cast.
•
Multi-cast connection:
Select when the same data is shared by multiple nodes.
This setting is usually used.
•
Point-to-Point connection:
Select when the same data is not shared by multiple
nodes. In a unicast transmission, other nodes are not
burdened with an unnecessary load.
Note
for details on using multi-cast and unicast
connections, and counting the number of connections.
The Connection Structure Area and the following items are not displayed if the
Hide Detail
Button is clicked.
Packet Interval (RPI)
Set the data update cycle (i.e., the packet interval) of each connection between the
originator and target. The default setting is 50 ms (i.e., data is updated once every 50
ms).
Set the RPI to between 1 and 10,000 ms in 1-ms increments.
Timeout Value
Set the time until a connection timeout is detected. The timeout value is set as a multi-
ple of the packet interval (RPI) and can be set to 4, 8, 16, 32, 64, 128, 256, or 512 times
the packet interval. The default setting is 4 times the packet interval (RPI).
Connection Name
Set a name for the connection. (32 single-byte characters max.)