8-57
8 CIP Message Communications
NY-series Industrial Panel PC / Industrial Box PC Built-in EtherNet/IP Port User’s Manual (W563)
8-
7 V
a
riab
le Dat
a T
ypes
8
8-7
-1 Dat
a T
yp
e Codes
8-7
Variable Data Types
This section provides the data types of variables that can be used with CIP message communications.
The following codes are given to variable data types.
* “CIP Common” indicates codes that are defined in the CIP Common Specifications. “Vendor Specific” indicates
codes that are assigned by OMRON.
8-7-1
Data Type Codes
Data Type
Code(Hex)
Group*
Boolean (bit)
C1
CIP Common
SINT (1-byte signed binary)
C2
CIP Common
INT (1-word signed binary)
C3
CIP Common
DINT (2-word signed binary)
C4
CIP Common
LINT (4-word signed binary)
C5
CIP Common
USINT (1-byte unsigned binary)
C6
CIP Common
UINT (1-word unsigned binary)
C7
CIP Common
UDINT (2-word unsigned binary)
C8
CIP Common
ULINT (4-word unsigned binary)
C9
CIP Common
REAL (2-word floating point)
CA
CIP Common
LREAL (4-word floating point)
CB
CIP Common
STRING
D0
CIP Common
BYTE (1-byte hexadecimal)
D1
CIP Common
WORD (1-word hexadecimal)
D2
CIP Common
DWORD (2-word hexadecimal)
D3
CIP Common
TIME (8-byte data)
DB
CIP Common
LWORD (4-word hexadecimal)
D4
CIP Common
Abbreviated STRUCT
A0
CIP Common
STRUCT
A2
CIP Common
ARRAY
A3
CIP Common
UINT BCD (1-word unsigned BCD)
04
Vendor Specific
UDINT BCD (2-word unsigned BCD)
05
Vendor Specific
ULINT BCD (4-word unsigned BCD)
06
Vendor Specific
ENUM
07
Vendor Specific
DATE_NSEC
08
Vendor Specific
TIME_NSEC
09
Vendor Specific
DATE_AND_TIME_NSEC
0A
Vendor Specific
TIME_OF_DAY_NSEC
0B
Vendor Specific
Union
0C
Vendor Specific
Summary of Contents for Sysmac NY512-1300