Appendices
A-34
NY-series Industrial Panel PC / Industrial Box PC Built-in EtherNet/IP Port User’s Manual (W563)
•
Connection Status Tab Page
Current status of each connection is given.
•
Tag Status Tab Page
This tab page gives if the tag settings for each tag for EtherNet/IP connections are set so that
data can be exchanged with target devices.
Name
Description
Connection Name
Gives the current status of each connection with the following text colors.
Blue: Normal
Red: There is at least one connection that has not been established.
Gray: There are no connections or the connection operation is stopped.
Type
Gives the connection type.
Status
Gives the current status on each connection with codes.
•
Normal operation: 00:0000
•
Abnormal operation: Gives an error code.
This information can be used to identify the cause of EtherNet/IP con-
nection errors. Refer to
14-2 Connection Status Codes and Trouble-
on page 14-9 for details on the connection status.
Name
Description
Tag Name
The current status of each tag is indicated by its color.
Red: Tag name resolution error
Blue: Tag name resolution normal
Gray: Not yet transferred (no information in device).
Input/Output
Gives the type of the tag.
Status
The following status is displayed depending on the status that is set.
•
Normally resolved: Normal data exchange is possible.
•
Different sizes: Different sizes are set for the network variables and the
tag settings.
A connection will not be established for a tag for which this error
occurs.
•
No tag: A network variable is not set in the variable table in the Con-
troller for the specified tag setting.
A connection will not be established for a tag for which this error
occurs.
•
Attribute error: The following two factors cause this error.
1. Writing is not possible for Constant attributes.
2. The I/O direction that is set in the tag data link settings does not
agree with the I/O direction of the variable in the Controller. There is
an error in the setting of a Network Publish attribute for a Controller
variable.
A connection will not be established for a tag for which this error
occurs.