![background image](http://html.mh-extra.com/html/omron/sysmac-ny512-1300/sysmac-ny512-1300_user-manual_742451104.webp)
5 Sysmac Studio Settings for the Built-in EtherNet/IP Port
5-4
NY-series Industrial Panel PC / Industrial Box PC Built-in EtherNet/IP Port User’s Manual (W563)
Default Gateway
*1 Even if you select
Fixed setting
for both EtherNet/IP port and internal port, you can only set the default gate-
way for one of the ports.
IP Router Table
Additional Information
IP Router Table Setting Example
To enable the Controller in an NY-series Industrial PC to perform Ethernet communications with
node B to send a CIP message etc. through an IP router, set the IP router table of the Controller
as follows.
When you set the IP router table, Controller sends packets to the gateway IP address
(130.25.36.253) if communications instructions are executed on Controller and addressed to
node B.
On the other hand, for Windows in an NY-series Industrial PC to perform Ethernet communica-
tions with node B to send a CIP message etc. through the Controller in an NY-series Industrial
PC and an IP router, you need to set the default gateway and other settings for IP routing in Win-
dows, in addition to the IP router table of the Controller.
Setting
Description
Default
Default gateway
Set the IP address of the default gateway for the built-in
EtherNet/IP port. This setting is not required when the
default gateway is not used.
*1
None
Parameter
Description
Default
Destination IP address
Set these settings when the built-in EtherNet/IP port is used
for tag data links or CIP message communications with
nodes on other IP network segments via an IP router. Set
them also to use the IP routing function of the built-in Ether-
Net/IP port as an IP router.
You can set up to 128 combinations of IP addresses and
gateway addresses.
Specify 0 for the host portions of the IP addresses.
None
Destination mask IP
address
Gateway address
None
The host fields are set to 0 in the destination IP address.
Windows
Controller
NY-series Industrial PC
130. 25. XX. XX
Node B
130. 26. XX. XX
130.25.36.253
130.26.2.254
IP router or NX-series Controller
Built-in
EtherNet/IP port
Internal port
Internal port
Summary of Contents for Sysmac NY512-1300
Page 459: ......